heat airflow for 90, 120, 150, or 180 seconds (depending
on selection at blower- -OFF delay switches). The furnace
control CPU is factory- -set for a 120- -second blower- -OFF
delay.
2. Two- -Stage Thermostat and Two- -Stage Heating
See Fig. 35 and 36 for thermostat connections.
NOTE: In this mode the low- -heat only switch SW1- -2 must be
ON to select the low- -heat only operation mode in response to
closing the thermostat R- -to- -W1 circuit. Closing the thermostat
R- -to- - W1- -and- -W2 circuits always causes high- -heat operation,
regardless of the setting of the low- -heat only switch.
The wall thermostat “calls for heat”, closing the R- -to- -W1 circuit
for low- -heat or closing the R- -to- -W1- -and- -W2 circuits for
high- -heat. The furnace control performs a self- -check, verifies the
low- -heat and high- -heat pressure switch contacts LPS and HPS are
open, and starts the inducer motor IDM in high- -speed.
The start up and shut down functions and delays described in item
1. above apply to the 2- -stage heating mode as well, except for
switching from low- - to high- -Heat and vice versa.
a. Switching from Low- - to High- -Heat - - If the thermostat
R- -to- -W1 circuit is closed and the R- -to- -W2 circuit closes,
the furnace control CPU will switch the inducer motor
IDM speed from low to high. The high- -heat pressure
switch relay HPSR is de- -energized to close the NC contact.
When sufficient pressure is available the high- -heat pres-
sure switch HPS closes, and the high- -heat gas valve
solenoid GV- -HI is energized. The blower motor BLWM
will transition to high- -heat airflow five seconds after the
R- -to- -W2 circuit closes.
b. Switching from High- - to Low- -Heat - -If the thermostat
R- -to- - W2 circuit opens, and the R- -to- -W1 circuit remains
closed, the furnace control CPU will switch the inducer
motor IDM speed from high to low. The high- -heat pres-
sure switch relay HPSR is energized to open the NC contact
and de- -energize the high- -heat gas valve solenoid GV- -HI.
When the inducer motor IDM reduces pressure suffi-
ciently, the high- -heat pressure switch HPS will open. The
gas valve solenoid GV- -M will remain energized as long
as the low- -heat pressure switch LPS remains closed. The
blower motor BLWM will transition to low- -heat airflow
five seconds after the R- -to- -W2 circuit opens.
3. Cooling mode
The thermostat “calls for cooling”.
a. Single- -Speed Cooling- -
See Fig. 35 and 36 for thermostat connections
The thermostat closes the R- -to- -G- -and- -Y circuits. The
R- -to- - Y circuit starts the outdoor unit, and the R- -to- -
G- -and- -Y/Y2 circuits start the furnace blower motor
BLWM on cooling airflow. Cooling airflow is based on the
A/C selection shown in Fig. 58. The electronic air cleaner
terminal EAC- -1 is energized with 115 vac when the
blower motor BLWM is operating.
When the thermostat is satisfied, the R- -to- -G- -and- -Y
circuits are opened. The outdoor unit will stop, and the
furnace blower motor BLWM will continue operating at
cooling airflow for an additional 90 seconds. Jumper Y/Y2
to DHUM to reduce the cooling off- -delay to 5 seconds.
See Fig. 35.
b. Single- -Stage Thermostat and Two- -Speed Cooling
(Adaptive Mode) - -
See Fig. 35 and 36 for thermostat connections.
This furnace can operate a two- -speed cooling unit with a
single- -stage thermostat because the furnace control CPU
includes a programmed adaptive sequence of controlled
operation, which selects low- -cooling or high- -cooling
operation. This selection is based upon the stored history