L. Install Horizontal Termination Cap (DVP
and SLP Pipe)
WARNING! Risk of Fire! The telescoping fl ue section of
the termination cap MUST be used when connecting vent.
• 1-1/2 (38 mm) minimum overlap of fl ue telescoping
section is required.
Failure to maintain overlap may cause overheating and
fi re.
• Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
• Flash and seal as appropriate for siding material at
outside edges of cap.
• When installing a horizontal termination cap, follow
the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.
CAUTION! Risk of Burns! Local codes may require in-
stallation of a cap shield to prevent anything or anyone
from touching the hot cap.
NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a fl ashing kit and
HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
52
Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. U • 7/12
Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield fi restop is
required on the exterior side of a combustible wall.
HEAT SHIELD OR
EXTENDED
HEAT SHIELD
WALL SHIELD
FIRESTOP
CAN BE EXTENDED
INNER VENT
OUTER VENT
VENT DEPTH FROM BACK OF APPLIANCE TO
OUTSIDE SURFACE OF EXTERIOR WALL
(SEE CHART BELOW)
Figure 10.20 Venting through the wall
Termination Cap Specifi cation Chart
(depth without using additional pipe sections)
DVP-TRAPK1
DVP-TRAP1
Top Vent
Rear Vent
Depth
Depth
3-1/8 in. to
N/A
SL Series
DVP-HPC1
DVP-HPC1
Top Vent
Rear Vent
Depth
Depth
3-1/8 in. to
N/A
5-1/4 in.
DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8)
DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8)
DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)
DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)
HEAT SHIELD
1-1/2 IN. (38 MM) MIN.
OVERLAP
SLIP SECTION
SHEATHING
INTERIOR
EXTERIOR
DVP-TRAPK2
DVP-TRAP2
Top Vent
Rear Vent
Depth
Depth
5-1/2 in. to
N/A
5 in.
9-1/2 in.
DVP-HPC2
DVP-HPC2
Top Vent
Rear Vent
Depth
Depth
5-1/4 in. to
N/A
9-3/8 in.