Mantel And Wall Projections - Heat & Glo SL-550TR-E Owner's Manual

Hide thumbs Also See for SL-550TR-E:
Table of Contents

Advertisement

B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materi-
als (i.e., steel studs, concrete board, etc.) Failure to comply
could cause fi re.
CEILING
All measurements are in inches.
12
11
10
9
8
32
7
6
5
13
4
12
11
3
10
9
8
7
6
5
4
TOP OF HOOD OR FIREPLACE OPENING
Figure 13.12 Clearances to Mantels or other Combustibles
above Appliance
1/2 in. SHEETROCK
OR COMBUSTIBLE
MATERIAL
3-1/2 in.
1/2 in.
NON-COMBUSTIBLE ZONE
Figure 13.13 Non-Combustible Zone
Models: SL-550TR-E, SL-750TR-E
SL-550TR-IPI-E, SL-750TR-IPI-E
1/2 IN.
MINIMUM
2-7/8 IN.
MINIMUM
3 FT. MAXIMUM
Note: Clearance from opening
to perpendicular wall.
Figure 13.14 Mantel Leg (Acceptable on both sides of opening.)
3 IN.
MINIMUM
5-3/8 IN.
MINIMUM
UNLIMITED
Note: Clearance from opening
to perpendicular wall.
Figure 13.15 Wall Projection (Acceptable on one side of opening.)
1/2 in.
SHEETROCK
3-1/2 in.
NON-COMBUSTIBLE
BOARD SHIPPED
WITH APPLIANCE
1/2 in.
Figure 13.16 Non-Combustible Zone
Models: SL-950TR-E, SL-950TR-IPI-E
Page 56