Fujitsu AS* G09LECB Service Instruction
Fujitsu AS* G09LECB Service Instruction

Fujitsu AS* G09LECB Service Instruction

Split type room air conditioner, wall mountedtype inverter

Advertisement

SERVICE
INSTRUCTION
R410A
SPLIT TYPE
ROOM AIR CONDITIONER
WALL MOUNTED
INVERTER
Models
Indoor unit
AS* G09LECB
AS* G12LECB
type
Outdoor unit
AO* G09LECAN
AO* G12LECAN

Advertisement

Table of Contents
loading

Summary of Contents for Fujitsu AS* G09LECB

  • Page 1: Wall Mounted Type

    SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTED type INVERTER SERVICE INSTRUCTION Models Indoor unit Outdoor unit AO* G09LECAN AS* G09LECB AO* G12LECAN AS* G12LECB R410A...
  • Page 2: Table Of Contents

    CONTENTS 1. DESCRIPTION OF EACH CONTROL OPERATION 1. COOLING OPERATION....................01-01 2. HEATING OPERATION....................01-02 3. DRY OPERATION......................01-03 4. AUTO CHANGEOVER OPERATION................01-04 5. INDOOR FAN CONTROL....................01-05 6. OUTDOOR FAN CONTROL..................01-07 7. LOUVER CONTROL..................... 01-08 8. COMPRESSOR CONTROL..................01-09 9.
  • Page 3: Description Of Each Control Operation

    R410A WALL MOUNTED type INVERTER 1 . DESCRIPTION OF EACH CONTROL OPERATION...
  • Page 4: Cooling Operation

    1. COOLING OPERATION 1-1 COOLING CAPACITY CONTROL A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation speed of the compressor. * If the room temperature is 2°C higher than a set temperature, the compressor operation speed will attain to maximum performance.
  • Page 5: Heating Operation

    2. HEATING OPERATION 2-1 HEATING CAPACITY CONTROL A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation speed of the compressor. * If the room temperature is lower by 3°C than a set temperature, the compressor operation speed will attain to maximum performance.
  • Page 6: Dry Operation

    3. DRY OPERATION 3-1 INDOOR UNIT CONTROL The compressor rotation frequency shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit body has detected as shown in the Table 3. However, the compressor frequency after the start-up is 56rps for 80seconds.
  • Page 7: Auto Changeover Operation

    4. AUTO CHANGEOVER OPERATION When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum mode from among the Heating, Cooling, Dry and Monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set between 18°C and 30°C in 1°C steps.
  • Page 8: Indoor Fan Control

    5. INDOOR FAN CONTROL 1. FAN SPEED ( Table 5 : Indoor fan speed ) AS*G09/12LECB Operation mode Air flow mode Speed (rpm) 1440 Heating 1370 1200 Quiet Cool air prevention S-Lo Cooling/ Fan 1440 1200 Quiet *Note, during Economy operation and operation mode is Fan, * Soft Quiet air flow is 1 step downs.
  • Page 9 6. COOL AIR PREVENTION CONTROL (Heating mode) The maximum value of the indoor fan speed is set as shown in Fig. 6, based on the detected temperature by the indoor heat exchanger sensor on heating mode. (Fig.6 : Cool air prevention control) <Before 7 minutes upon running the compressor>...
  • Page 10: Outdoor Fan Control

    6. OUTDOOR FAN CONTROL 1. Outdoor Fan Motor Following table shows the type of the outdoor fan motor. The control method is different between AC motor and DC motor. ( Table7 : Type of Motor ) AC Motor DC Motor AO*G09/ 12LECAN 2.
  • Page 11: Louver Control

    7. LOUVER CONTROL 1. VERTICAL LOUVER CONTROL (Function Range) Each time the button is pressed, the air direction range will change as follow: (Fig 9: Air Direction Range) Cooling / Dry mode / Heating mode / Fan mode Use the air direction adjustments within the ranges shown above. The vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
  • Page 12: Compressor Control

    8. COMPRESSOR CONTROL 1. OPERATION SPEED RANGE The operation speed of the compressor is different based on the operation mode as shown in the Table 10. (Table 10 : Compressor operation speed range) Cooling Heating Minimum Maximum Minimum Maximum Minimum Maximum AO*G09LECAN 18rps...
  • Page 13: Timer Operation Control

    9. TIMER OPEARTION CONTROL 9-1 WIRELESS REMOTE CONTROLLER The Table 12 shows the available timer setting based on the product model. (Table 12 : Timer setting) ON TIMER / OFF TIMER PROGRAM TIMER SLEEP TIMER AS* G09/ 12LECB 1. OPEARTION FREQUENCY RANGE OFF timer : When the clock reaches the set time, the air conditioner will be turned off.
  • Page 14 3. SLEEP TIMER If the sleep is set, the room temperature is monitored and the operation is stopped automatically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time ON. In the cooling operation mode When the sleep timer is set, the setting temperature is increased 1°C.
  • Page 15 9-2 WIRED REMOTE CONTROLLER (OPTION) The Table13 shows the available timer setting based on the product model. ( Table13 : Timer Setting ) ON TIMER / OFF TIMER WEEKLY TIMER TEMPERATURE SET BACK TIMER AS* G09/ 12LECB ON TIMER / OFF TIMER Same to 9-1 1.ON TIMER / OFF TIMER and shown in those.
  • Page 16: Electronic Expansion Valve Control

    10. ELECTRONIC EXPANSION VALVE CONTROL The most proper opening of the electronic expansion valve is calculated and controlled under the present operating condition based on the following values. The compressor frequency, the temperatures detected by the discharge temperature sensor, the indoor heat exchanger sensor, the outdoor heat exchanger sensor, and the outdoor temperature sensor.
  • Page 17: Manual Auto Operation (Indoor Unit Body Operation)

    15. MANUAL AUTO OPERATION (Indoor unit body operation) If MANUAL AUTO Button is set, the operation is controlled as shown in Table14. If the remote control is lost or battery power dissipated, this function will work without the remote control. (Table 14) Manual auto operation OPERATION MODE...
  • Page 18: C Heat Operation

    18. 10°C HEAT OPERATION The 10°C HEAT operation functions by pressing 10°C HEAT button on the remote controller. The 10°C HEAT operation is almost the same operation as below settings. ( Table16 ) Mode Heating Setting temperature 10°C Fan mode Auto 19.
  • Page 19: Defrost Operation Control

    21. DEFROST OPERATION CONTROL 1. CONDITION OF STARTING THE DEFROST OPERATION The defrost operation starts when the outdoor heat exchanger temperature sensor (Tn) detects the temperature lower than the values shown in Table 18. (Table 18 : Condition of starting Defrost Operation) Compressor integrating operation time Normal defrost Less than 35 minutes...
  • Page 20 3. Defrost Flow Chart The defrosting shall proceed by the integrating operation time, outdoor temperature and outdoor heat exchanger temperature as follows. Heating operation start : Compressor ON (Not defrosted for 10 minutes) Integrating defrost Normal defrost Outside temp.< -20°C utside temp.
  • Page 21: Off Defrost Operation Control

    22. OFF DEFROST OPEARTION CONTROL When operation stops in the [Heating operation] mode, if frost is adhered to the outdoor unit heat exchanger, the defrost operation will proceed automatically. In this time, if indoor unit operation lamp flashes slowly (7 sec ON / 2 sec OFF), the outdoor unit will allow the heat exchanger to defrost, and then stop.
  • Page 22: Various Protections

    23. VARIOUS PROTECTIONS 1. DISCHARGE GAS TEMPERATURE OVERRISE PREVENSION CONTROL The discharge discharge thermistor will detect discharge gas temperature. 1-1. When the discharge temperature becomes higher than Temperature , the compressor speed is decreased 20rps, and it continues to decrease the speed for 20rps every 120seconds until the temperature becomes lower than Temperature .
  • Page 23 3. ANTIFREEZING CONTROL (Cooling and Dry mode) The compressor speed is decreased on cooling & dry mode when the indoor heat exchanger temperature sensor detects the temperature lower than Temperature . Then, the anti-freezing control is released when it becomes higher than Temperature . (Table 22 : Anti-freezing protection operation / Release temperature) Outdoor temperature Temperature...
  • Page 25: Trouble Shooting

    R410A WALL MOUNTED type INVERTER 2 . TROUBLE SHOOTING...
  • Page 26: Error Display

    2. TROUBLESHOOTING 2-1 ERROR DISPLAY 2-1-1 INDOOR UNIT AND WIRED REMOTE CONTROLLER DISPLAY Please refer the flashing pattern as follows. Indoor Unit : AS*G 09/ 12LECB The OPERATION, TIMER and ECONOMY lamps operate as follows according to the error contents. Indoor Unit Display Wired Remote Trouble...
  • Page 27: Wired Remote Controller Display (Option)

    2-1-2 WIRED REMOTE CONTROLLER DISPLAY (OPTION) 1. SELF - DIAGNOSIS When " Er " in Temperature Display is displayed, inspection of the air conditioning system is necessary. Please consult authoilzed servise personnel. Unit number (usually 0) Error code SU MOTU WETH FR SA ex.
  • Page 28: Trouble Shooting With Error Code

    2-2 TROUBLE SHOOTING WITH ERROR CODE Trouble shooting 1-1 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Serial communication error (Serial Reverse Transfer Error) Detective details: Detective Actuators: When the indoor unit cannot receive the serial signal from Outdoor unit Outdoor unit Main PCB more than 2minutes after power ON, or the indoor unit cannot receive Outdoor unit fan motor...
  • Page 29 Trouble shooting 1-2 Indicate or Display: INDOOR UNIT Error Method: Refer to error code table. Serial communication error (Serial Forward Transfer Error) Detective details: Detective Actuators: When the outdoor unit cannot receive the serial signal from Indoor unit Indoor unit Controller PCB more than 10seconds.
  • Page 30 Trouble shooting 2 Indicate or Display: INDOOR UNIT Error Method: Remote controller communication Refer to error code table. error Detective details: Detective Actuators: When the indoor unit cannot receive the signal from Wired Remote Control Indoor unit Controller PCB more than 1minute during normal operation. Wired remote control Forecast of Cause: 1.
  • Page 31 Trouble shooting 3 Indicate or Display: INDOOR UNIT Error Method: Refer to error code table. Indoor unit main PCB error Detective details: Detective Actuators: When power is on and there is some below case. Indoor unit Controller PCB 1. When model information of EEPROM is incorrect. 2.
  • Page 32 Trouble shooting 4 Indicate or Display: INDOOR UNIT Error Method: INDOOR UNIT Refer to error code table. Manual auto switch error Detective Actuators: Detective details: Indoor unit Controller PCB When the Manual Auto Switch becomes ON for consecutive 60 or more seconds.
  • Page 33 Indicate or Display: Trouble shooting 5 INDOOR UNIT Error Method: INDOOR UNIT Refer to error code table. Room temperature sensor error Detective Actuators: Detective details: Indoor unit Controller PCB When Room Temperature Thermistor open or short-circuit is detected. Room temperature thermistor Forecast of Cause : 1.
  • Page 34 Trouble shooting 6 Indicate or Display: INDOOR UNIT Error Method: INDOOR UNIT Refer to error code table. Indoor unit Heat Ex. sensor error Detective Actuators: Detective details: Indoor unit Controller PCB When Heat Ex. Temperature Thermistor open or short-circuit is detected. Heat Ex.
  • Page 35 Trouble shooting 7 Indicate or Display: INDOOR UNIT Error Method: Refer to error code table. Indoor unit fan motor error Detective Actuators: Detective details: When the condition that actual frequency of Indoor Fan is Indoor unit Controller PCB below 1/3 of target frequency is continued more than 56 seconds. Indoor unit Fan motor Forecast of Cause: 1.
  • Page 36 Trouble shooting 9 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Outdoor unit main PCB error Detective details: Detective Actuators: Access to EEPROM failed due to some cause after outdoor unit started. Outdoor unit Main PCB Forecast of Cause: 1.
  • Page 37 Trouble shooting 10 Indicate or Display: OUTDOOR UNIT Error Method: INDOOR UNIT Refer to error code table. PFC circuit error Detective Actuators: Detective details: When inverter output DC voltage is higher than 415V for over 3 seconds, Outdoor unit Main PCB the compressor stops.
  • Page 38 Trouble shooting 11 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. IPM error Detective details: Detective Actuators: When more than normal operating current to IPM in Main PCB flows, Outdoor unit Main PCB the compressor stops. Compressor After the compressor restarts, if the same operation is repeated within 40sec, the compressor stops again.
  • Page 39 Trouble shooting 12 Indicate or Display: OUTDOOR UNIT Error Method: INDOOR UNIT Refer to error code table. Discharge thermistor error Detective details: Detective Actuators: When Discharge pipe temperature thermistor open or short-circuit Outdoor unit Main PCB is detected at power ON or while running the compressor. Discharge pipe temperature thermistor Forecast of Cause : 1.
  • Page 40 Trouble shooting 13 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Outdoor unit Heat Ex. sensor error Detective details: Detective Actuators: Outdoor unit Main PCB When Heat exchanger temperature thermistor open or Heat exchanger temperature thermistor short-circuit is detected at power ON or while running the compressor.
  • Page 41 Trouble shooting 14 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Outdoor thermistor error Detective details: Detective Actuators: Outdoor unit Main PCB When Outdoor temperature thermistor open or short-circuit is Outdoor temperature thermistor detected at power ON or while running the compressor. Forecast of Cause : 1.
  • Page 42 Trouble shooting 15 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Current sensor error Detective Actuators: Detective details: When Input Current Sensor has detected 0A, while Inverter Compressor is Outdoor unit Main PCB operating at higher than 56rps, after 1minute upon starting the Compressor. (Except during the defrost operation) Forecast of Cause : 1.
  • Page 43 Trouble shooting 16 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Trip detection Detective details: Detective Actuators: "Protection stop by overcurrent generation after inverter compressor start Outdoor unit Main PCB processing completed'' generated consecutively 10 times. Compressor * The number of generations is reset if the start-up of the compressor succeeds.
  • Page 44 Trouble shooting 17 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Compressor motor control error Detective details: Detective Actuators: If the detected rotor location is out of phase with actual rotor location Outdoor unit Main PCB more than 90°, the compressor stops.
  • Page 45 Trouble shooting 18 Indicate or Display: OUTDOOR UNIT Error Method: Refer to error code table. Outdoor unit fan motor error Detective Actuators: Detective details: When outdoor fan rotation speed is less than 100rpm in 20 seconds Outdoor unit Main PCB after fan motor starts, fan motor stops.
  • Page 46 Trouble shooting 19 Indicate or Display: INDOOR UNIT Error Method: Refer to error code table. 4-way valve error Detective Actuators: Detective details: When the indoor heat exchanger temperature is compared with Indoor unit Controller PCB the room temperature, and either following condition is detected Heat Ex.
  • Page 47 Trouble shooting 20 Indicate or Display: OUTDOOR UNIT Error Method: INDOOR UNIT Discharge temperature error Refer to error code table. Detective details: Detective Actuators: Outdoor unit Main PCB "Protection stop by "discharge temperature 110degC during compressor operation"" generated 2 times within 24 hours. Discharge temperature thermistor Forecast of Cause : 1.
  • Page 48: Trouble Shooting With No Error Code

    2-3 TROUBLE SHOOTING WITH NO ERROR CODE Forecast of Cause: Trouble shooting 21 1. Power supply failure 2. External cause Indoor Unit - No Power 3. Electrical components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable.
  • Page 49 Forecast of Cause: Trouble shooting 22 1. Power supply failure 2. External cause Outdoor Unit - No Power 3. Electrical Components defective Check Point 1 : Check Installation Condition Isn’t the breaker down? Check loose or removed connection cable. >>If abnormal condition is found, correct it by referring to Installation Manual or Data &...
  • Page 50 Forecast of Cause: Trouble shooting 23 1. Setting/ Connection failure 2. External cause No Operation (Power is ON) 3. Electrical component defective Check Point 1 : Check indoor and outdoor installation condition Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control. Or, check if there is an open cable connection.
  • Page 51 Forecast of Cause: Trouble shooting 24 1. Indoor Unit error 2. Outdoor Unit error No Cooling / No Heating 3. Effect by surrounding environment 4. Connection pipe / Connection wire failure 5. Refrigeration cycle failure Check Point 1 : Check Indoor unit Does Indoor unit Fan run on High fan? Is Air filter dirty? Is Heat exchanger clogged?
  • Page 52 Forecast of Cause : Trouble shooting 25 1. Abnormal installation (Indoor/ Outdoor) Abnormal Noise 2. Fan failure (Indoor/ Outdoor) 3. Compressor failure (Outdoor) Diagnosis method when abnormal noise is occurred Abnormal noise is coming from Indoor unit. Abnormal noise is coming from Outdoor unit. (Check and correct followings) (Check and correct followings) Is Main unit installed in stable condition?
  • Page 53: Service Parts Information

    2-4 SERVICE PARTS INFORMATION SERVICE PARTS INFORMATION 1 Compressor Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting ) Abnormal noise Stops soon after starting up Does not start up Check if vibration noise by Is there open or loose connection Is there open or loose connection loose bolt or contact noise...
  • Page 54 SERVICE PARTS INFORMATION 2 Inverter Compressor Check Point 1 : Check Connection Check terminal connection of Compressor (loose or incorrect wiring) Terminal cover opened C(W) (BLACK) R(U) S(V) (RED) (WHITE) AO* G09/ 12LECAN Check Point 2 : Check Winding Resistance Check winding resistance of each terminal If the resistance value is 0 or infinite, replace Compressor.
  • Page 55 SERVICE PARTS INFORMATION 3 Outdoor unit Electronic Expansion Valve ( EEV ) Check Point 1 : Check Connections Check connection of connector (CN40) ( Loose connector or open cable ) EXPANSION VALVE COIL BLUE ORANGE CN40 YELLOW WHITE Check Point 2 : Check Coil of EEV Check Point 3 : Check Voltage from Main PCB.
  • Page 56 SERVICE PARTS INFORMATION 4 Indoor unit fan motor Check Point 1 : Check rotation of Fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) >>If Fan or Bearing is abnormal, replace it. Check Point 2 : Check resistance of Indoor Fan Motor Refer to below.
  • Page 57: Appending Data

    R410A WALL MOUNTED type INVERTER 3 . APPENDING DATA...
  • Page 58: Function Setting

    3-1. FUNCTION SETTING 3-1-1 INDOOR UNIT Follow the instructions in the Local Setup Procedure, which is supplied with the remote control, in accordance with the installed condition. After the power is turned on, perform the Function Setting on the remote control. The settings may be selected between the following two: Function Number or Setting Value.
  • Page 59 1-5. Setting the Indoor room temperature sensor switching function (Only for Wired remote controller) The following settings are needed when use the control by Wired remote controller temperature sensor. Factory setting) Setting Description Function Number Setting Value * If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor. * If setting value is "01"...
  • Page 60: Procedures To Change The Function Setting For Wireless Rc

    3-1-2 Procedures to change the Function Setting for wireless RC This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incorrect settings can cause the indoor unit malfunction. After the power is turned on, perform the "FUNCTION SETTING" according to the installation conditions using the remote controller.
  • Page 61 Custom code setting for remote controller (1) Press the MODE button for more then 5 seconds. (2) Press the SET TEMP. ( ) buttons to change the signal code between Match the code on the display to the air conditioner signal code. (initially set to (3) Press the MODE button.
  • Page 62: Thermistor Resistance Values

    3-2. Thermistor Resistance Values 3-2-1 INDOOR UNIT Room temperature thermistor Indoor heat exchanger thermistor Temp ( C) Resistance(k ) Voltage(V) Temp ( C) Resistance(k ) Voltage(V) -10.0 58.2 0.73 -5.0 233.2 0.88 -5.0 44.0 0.93 176.0 1.10 33.6 1.15 134.2 1.36 25.9 1.39...
  • Page 63 1116,Suenaga,Takatsu-ku,Kawasaki 213-8502,Japan Dec. 2012 Printed in Japan...