Kohler 6EKOD Installation Manual page 22

Marine generator sets
Hide thumbs Also See for 6EKOD:
Table of Contents

Advertisement

21
Waterline
20
17
1. Cap
2. Reed valve
3. Mounting base
4. Maximum silencer vertical lift of 1.2 m (4 ft.)
5. Exhaust mixer elbow distance above waterline; if less than
23 cm (9 in.), a siphon break is required
6. Minimum siphon break distance above waterline of 30.5 cm
(1 ft.)
7. Siphon break
8. Exhaust mixer elbow
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank (located on the unit on some models)
11. Seawater strainer
12. Seacock
13. Intake strainer
14. Engine-driven seawater pump
15. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.)
16. Maximum distance between silencer and exhaust mixer elbow
of 3 m (10 ft.)
17. Maximum distance between silencer and exhaust outlet of
1.5 m (5 ft.)
Figure 4-7 Typical Mid- and Below-Waterline Installation
22
Section 4 Exhaust System
1
2
3
4
19
18
22
7
6
5
15
16
18. Silencer (customer-supplied)
19. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
(0.5 in. per ft.)
20. Minimum exhaust outlet distance above waterline of 10 cm
(4 in.)
21. Exhaust hose (see Figure 4-5 for hose sizes)
22. If the total exhaust length exceeds 4.6 m (15 ft.), Kohler
recommends increasing the exhaust hose to the next larger
diameter. See Figure 4-2 and Figure 4-5.
Note: Read the text for complete explanation of dimensions and
other installation considerations.
Note: Use two hose clamps on each end of all flexible exhaust
hose connections.
Note: Data applies to both rear- and side-exhaust installations.
Note: Damage caused by water ingestion will not be covered by
the generator warranty.
8
9
14
13
TP-6773 5/12a
10
11
12
TP-5856-4