Section 3 Cooling System; Ventilation; Cooling System Components; Intake Through-Hull Strainer (Seacock Cover) - Kohler 6EKOD Installation Manual

Marine generator sets
Hide thumbs Also See for 6EKOD:
Table of Contents

Advertisement

3.1 Ventilation

Engine combustion, generator cooling, and expulsion of
flammable and lethal fumes require ventilation. Provide
ventilation compliant with USCG Regulations governing
sizing of vents and other considerations.
As a rule, size each inlet- and outlet-vent area to a
minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the
craft's beam.
Should this rule conflict with USCG
Regulations, follow USCG Regulations. For applications
with screened inlets, double the size (4 sq. in. per ft.) of
the hull/deck openings. Extend the vent ducts to bilges to
expel heavier-than-air fumes.
For generator sets mounted in the engine compartment,
increase the air flow to allow for the generator set's
requirements.
Install optional detection devices to
cause alarm, warning, or engine shutdown should
dangerous fumes accumulate in the compartment.
See the generator set specification sheet that shipped
with the generator set for air requirements. The air intake
silencer/cleaner provides combustion air to the engine.
Do not compromise the recommended minimum
clearance of 38 mm (1.5 in.) between a duct opening and
enclosure wall. The engine/generator performance will
decline if you compromise these guidelines.
Figure 3-1 for allowable intake restriction.
Note: ISO 3046 derates apply. See Appendix C.
Model
6EKOD/5EFKOD
9--11EKOZD/7--9EFKOZD
Figure 3-1 Combustion Air Intake Restriction

3.2 Cooling System Components

The marine generator set's cooling system requires the
following components.
TP-6773 5/12a
See
Allowable
Intake Restriction
250 mm
(10 in.) H
O or less
2

Section 3 Cooling System

3.2.1
Intake Through-Hull Strainer
(Seacock Cover)
Install a screened-intake, through-hull strainer to
prevent entry of foreign objects.
slotted-hole, or unrestricted-hole design strainers. See
Figure 3-2 for examples of typical strainers. The inner
diameter of the strainer opening must be equal to or
greater than the inner diameter of the water-line hose to
the seawater pump.
1
1. Inside packing
2. Outside packing
3. Seacock cover
4. Direction of vessel movement
5. Typical intake through-hull strainers
Figure 3-2 Seacock Installation
Do not align the strainer (in relation to the craft's direction
of travel) with any other through-hull intakes.
Figure 3-3. Flush mount the recommended through-hull
strainer. Install slotted-hole-design strainers with the
slots parallel to the direction of the vessel's movement.
Use perforated,
2
3
4
5982--3.1
5
Section 3 Cooling System
See
13

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

5efkod7-9efkozd9-11ekozd

Table of Contents