Capacity Control; Current Release Control - Toshiba RAS-10SKVP2-E Service Manual

Split type indoor unit high wall, heat pump type outdoor unit heat pump type
Table of Contents

Advertisement

Item
4. Capacity
The cooling or heating capacity depending on the load is
control
adjusted.
According to difference between the setup value of tempera-
ture and the room temperature, the capacity is adjusted by
the compressor revolution.
Remote controller
Set temp. (Ts)
Detection of electromotive force
Detection of motor speed and rotor position
Correction value of Hz signal ≤ Operating Hz
5. Current release
This function prevents troubles on the electronic parts of the
control
compressor driving inverter.
This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.
Outdoor unit inverter main
circuit control current
Operating current ≤
Setup value
Low
Capacity control continues.
Outdoor temp.
45ºC
44ºC
40ºC
16ºC
39ºC
11ºC
15.5ºC
10.5ºC
Operation flow and applicable data, etc.
Ts –Ta
Correction of Hz signal
of compressor motor winding
Inverter output change
Commutation timing change
Change of compressor speed
Setup of current release point
High
Reduce compressor speed
Cooling current release value
RAS-10SAVP2-E RAS-13SAVP2-E RAS-16SAVP2-E RAS-10SAVP2-E RAS-13SAVP2-E RAS-16SAVP2-E
4.27A
4.27A
6.75A
6.75A
8.47A
8.47A
Indoor unit
Room temp. (Ta)
Outdoor temp. To
Current decrease
Heating current release value
7.72A
6.45A
6.75A
8.47A
8.32A
8.92A
29
FILE NO. SVM-11015
Description
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
3) The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
4) According to the difference
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commuta-
tion timing are varied.
5) Change the compressor motor
speed by outputting power to the
compressor.
* The contents of control
operation are same in cooling
operation and heating
operation
1) The input current of the outdoor
unit is detected in the inverter
section of the outdoor unit.
2) According to the detected
outdoor temperature, the
specifice value of the current is
selected.
3) Whether the current value
exceeds the specifice value or
not is judged.
4) If the current value exceeds the
specified value, this function
reduces the compressor speed
and controls speed up to the
closest one commanded from the
indoor unit within the range
which does not exceed the
specified value.
7.72A
7.72A
9.22A
9.22A
10.80A
10.80A