Troubleshooting Guide - Millivolt - Lennox Hearth Products EBVCLNE Homeowner's Care And Operation Instructions Manual

B-vent multi-open elite series
Hide thumbs Also See for EBVCLNE:
Table of Contents

Advertisement

TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM
ote: Before troubleshooting, make sure that the appliance main line gas shut-off valve and the gas control valve are in the "OPEN"
N
position and the burner ON/OFF switch is in the "ON" position.
Important: Valve system troubleshooting should only be accomplished by a qualified service technician.
SYMPTOM
1. Spark ignitor will not light
pilot after repeated
triggering of ignitor button.
2. Pilot will not stay lit after
carefully following the
lighting instructions.
3. Pilot burning, no gas to
burner, Valve knob "ON,"
Wall Switch "ON."
4. Frequent pilot/burner outage
problem.
20
POSSIBLE CAUSES
A. Defective ignitor
(no spark at electrode).
B. Defective or misaligned electrode
at pilot (spark at electrode).
C. Gas supply pressure errant.
D. Pilot orifice plugged.
A. Defective pilot generator
(thermocouple).
A. Limit Switch defective.
B. Wall switch or wires defective.
C. Thermopile may not be generating
sufficient millivoltage.
D. Plugged burner orifice.
A. Pilot flame may be too low or
blowing (high) causing the pilot/
valve safety to drop out.
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.
CORRECTIVE ACTION
Check for spark at electrode and pilot; if no spark and
electrode wire is properly connected, replace ignitor.
Using a match, light pilot. If pilot lights, turn off pilot and
trigger the ignitor button again. If pilot lights, an improper gas
mixture caused the bad lighting and a longer purge period is
recommended. If pilot will not light – check gap at electrode
and pilot – should be
" to have a strong spark. If gap
measures
", replace pilot ( Figure 11 on page 10 ).
Check inlet gas pressure. It should be within the limits as
marked on the rating plate.
Clean or replace pilot orifice.
Check pilot flame, it must impinge on thermocouple ( Figure
11 on page 10 ) Clean and/or adjust pilot for maximum flame
impingement on thermocouple. Ensure that the connection
between the valve and thermocouple are tight and secure.
Isolate the "limit" switch. Disconnect the wires from the "ON/
OFF" switch and the valve (label wires for reattachment). Test
for continuity with a multimeter. If continuity is not indicated,
switch is defective and must be replaced.
Check wall switch and wires for proper connections. Jumper
wire across terminals at wall switch, if burner comes on,
replace defective wall switch. If okay, jumper wires across wall
switch wires at valve, if burner comes on, wires are faulty or
connections are bad.
Check thermopile with millivolt meter. Take reading at thermo-
pile terminals of gas valve. Should read 325 millivolts mini-
mum with optional wall switch "OFF." Replace faulty thermo-
pile if reading is below specified minimum.
Check burner orifice for stoppage and remove.
Clean and/or adjust pilot flame for maximum flame impinge-
ment on thermocouple ( Figure 11 on page 10 ).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents