Panasonic CS-E18NKUA Service Manual page 60

Hide thumbs Also See for CS-E18NKUA:
Table of Contents

Advertisement

15.4.14
F91 (Refrigeration Cycle Abnormality)
Malfunction Decision Conditions
During cooling, compressor frequency = Fcmax.
During cooling and heating operation, running current: 0.65A < I < 1.65A.
During cooling, indoor intake - indoor pipe < 39.2°F.
Malfunction Caused
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor.
2/3 way valve closed.
Detection error due to faulty indoor intake air or indoor pipe temperature sensors.
Troubleshooting
60