(3) Secure the cables using the cable clips under the terminal blocks, and then secure
the cables using the cable clips attached to the base of the valves.
(4) Be sure to install the insulation sheet after the wiring is complete.

7. PIPE INSTALLATION-2

s
Install the insulated pipes so that they do not touch the compressor.

7.1. Installing insulation

Use an insulation on the refrigerant pipes to prevent condensation and dripping.
(Fig. A)
Determine the thickness of the insulation material by referring to Table A.
Table A, Selection of insulation
(for using an insulation material with equal heat transmission rate or below
0.040 W/(m·k))
Relative humidity
[mm (in.)]
6.35 (1/4)
9.52 (3/8)
Pipe
12.70 (1/2)
diameter
15.88 (5/8)
19.05 (3/4)
If the ambient temperature and relative humidity exceed 32 °C, increase the level of heat
insulation for the refrigerant pipes.

7.2. Filling with putty

Fill the piping holes with putty (supplied locally) to avoid any gap (Fig A). If small animals
such as insects enter the external unit, a short circuit may be caused near electrical
components in the service panel.
If the outdoor unit is installed at a level that is higher than the indoor unit, the water that
has condensed in the 3-way valve of the outdoor unit could travel to the indoor unit.
Therefore, use putty in the space between the pipe and the insulation to prevent the entry
of water.
Fig. A
Putty
En-12
Cable clip
WARNING
Insulation material
Minimum thickness [mm]
70%
75%
80%
or more
or more
or more
10
13
8
11
14
9
10
12
15
10
12
16
10
13
16
WARNING
Insulation

8. HOW TO OPERATE DISPLAY UNIT

8.1. Various setting methods

Never touch electrical components such as the terminal blocks or reactor except the
switch on the display board. It may cause a serious accident such as electric shock.
Once refrigerant charging is completed, be sure to open the valve prior to performing
the local settings. Otherwise, the compressor may fail.
Discharge any static electricity from your body before touching the push switches. Never
touch any terminal or pattern of any parts on the control board.
The positions of the switches on the outdoor unit control board are shown in the figure
below.
d
Reactors
Various settings can be adjusted by changing DIP switches and push switches on the
board of the outdoor unit.
85%
or more
17
18
19
20
21
The printed characters for the LED display are shown below.
SW1
WARNING
CAUTION
Terminal blocks
LED display
DIP switch
LED display part
(1)
(2) (3) (4)
(5)
SW2
SW3
SW4
SW5
Push
switches
(6)
SW6