Electrical Control Function
15
Frequency limit symbol
16
DC fan motor speed
17
IGBT radiator temp.(Reserved)
18
Indoor unit number
19
Condenser pipe temp. of 1# indoor unit
20
Condenser pipe temp. of 2# indoor unit
21
Condenser pipe temp. of 3# indoor unit
22
1# Indoor unit capacity demand code
23
2# Indoor unit capacity demand code
24
3# Indoor unit capacity demand code
116
For example ,the digital display tube show "2.0",it means the
EXV open angle is 120×4=480p.)
Frequency limit
Bit7
caused by IGBT
radiator
Frequency limit
Bit6
caused by PFC
Frequency limit
Bit5
caused by T4.
Frequency limit
Bit4
caused by T2.
Frequency limit
Bit3
caused by T3.
Frequency limit
Bit2
caused by Tp.
Frequency limit
Bit1
caused by current
Frequency limit
Bit0
caused by voltage
The display value is between 30~120 degree. If the temp. is
lower than 30 degree, the digital display tube will show "30".If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show "0.5",it means the IGBT radiator temp. is
105 degree. the digital display tube show "1.6",it means the
IGBT radiator temp. is 116 degree)
The indoor unit can communicate with outdoor unit well.
If the temp. is lower than 0 degree, the digital display tube will
show "0".If the temp. is higher than 70 degree, the digital
display tube will show "70". If the capacity demand is 0, , the
digital display tube will show "0. If the indoor unit is not
connected, the digital display tube will show: "――"
Norm code *HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show "5.0",it means the capacity demand
is 15. the digital display tube show "60",it means the capacity
demand is 6.0). If the indoor unit is not connected, the digital
display tube will show: "――"
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.
Electrical Control System