Field Wiring; Hydrobox Powered Via Outdoor Unit; Electrical Connections 1 Phase; Electrical Connections 3 Phase - Mitsubishi Electric EHSD-MEC.UK Service Manual

R410a hydrobox
Hide thumbs Also See for EHSD-MEC.UK:
Table of Contents

Advertisement

7

FIELD WIRING

Breaker abbreviation
Meaning
ECB1
Earth leakage circuit breaker for booster heater
TB1
Terminal block 1
Option 1: Hydrobox powered via outdoor unit
<1 phase>
Affix label A that is included with the manuals near each wiring diagram for hydrobox and outdoor units.
Power
Earth
supply
leakage
~/N
circuit
breaker or
breaker
230 V
*1
50 Hz

Electrical connections 1 phase

<3 phase>
Affix label A that is included with the manuals near each wiring diagram for hydrobox and outdoor units.
Earth
Power
leakage
supply
circuit
3N~
breaker
400 V
*1
50 Hz
Power supply
3~ 400 V 50 Hz (EH**-YM9(E)C)
3~ 230 V 50 Hz (EHSC-TM9C)

Electrical connections 3 phase

Hydrobox - Outdoor unit
Hydrobox - Outdoor unit earth
Hydrobox - Outdoor unit S1 - S2
Hydrobox - Outdoor unit S2 - S3
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
*3. The values given in the table above are not always measured against the ground value.
Notes:
1. Wiring size must comply with the applicable local and national codes.
2. Indoor unit/outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)
Indoor unit power supply cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60227 IEC 53)
3. Install an earth longer than other cables.
4. Please keep enough output capacity of power supply for each heater. Insufficient power supply capacity might cause chattering.
OCH571
Outdoor unit
L
S1
Wiring
circuit
N
S2
Isolating
S3
switch
Power
Wiring
supply ~/
circuit
N
breaker or
230 V
Isolating
50 Hz
switch
<Figure 7-1>
Outdoor unit
L1
L2
Wiring
circuit
L3
breaker or
Isolating
N
switch
Wiring
circuit
breaker or
Isolating
switch
<Figure 7-2>
*2
3 × 1.5 (polar)
*2
1 × Min. 1.5
*3
230 V AC
*3
Hydrobox
TB1
L
N
To control
board
S1
S2
S3
ECB1
For
L
booster
heater
N
(Primary circuit)
Hydrobox
TB1
L1
L2
To control
board
S1
S1
S2
S2
S3
S3
ECB1
L1
For
booster
L2
heater
(Primary circuit)
L3
24 V DC
16
*1 If the installed earth leakage circuit breaker does
not have an over-current protection function, install a
breaker with that function along the same power line.
Description
Power supply Capacity Breaker
2 kW
Booster heater
~/N 230 V
(Primary circuit)
50 Hz
6 kW
*1 If the installed earth leakage circuit breaker does
not have an over-current protection function, install
a breaker with that function along the same power
line.
Description
Power supply Capacity Breaker
3~ 400 V
9 kW
50 Hz
Booster heater
(Primary circuit)
3~ 230 V
9 kW
50 Hz
Wiring
16 A *1 2.5 mm²
32 A *1 6.0 mm²
Wiring
16 A *1 2.5 mm²
32 A *1 6.0 mm²