Recharging Of Refrigerant; Configuration Of Refrigerant Charging; Tools - Toshiba Carrier RAV-SP180AT2-UL Service Manual

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

6-3. Tools

6-3-1. Required Tools
Refer to the "4. Tools" (Page 8)

6-4. Recharging of Refrigerant

When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps.
Recover the refrigerant, and check no refrigerant remains
in the equipment.
Connect the charge hose to packed valve service port at
the outdoor unit's gas side.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully
opened position, and turn on the vacuum pump's power
switch. Then, evacuating the refrigerant in the cycle.
1) Never charge refrigerant exceeding the specified amount.
2) If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3) Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified
amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and
may cause a rupture or personal injury.
Refrigerant cylinder
(With siphon pipe)
Electronic balance for refrigerant charging
(INDOOR unit)
(Liquid side)
Check valve
Open/Close valve
for charging
Fig. 6-4-1 Configuration of refrigerant charging
– 27 –
When the compound gauge's pointer has indicated
–101 kpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump's
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge's pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
Opened
(Gas side)
Closed
Service port
(OUTDOOR unit)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents