Outdoor Unit - Toshiba Carrier RAV-SP180AT2-UL Service Manual

Ac split type outdoor unit super digital inverter
Hide thumbs Also See for Carrier RAV-SP180AT2-UL:
Table of Contents

Advertisement

3-2. Outdoor Unit

RAV-SP180AT2-UL
TS
TD
sensor
sensor
Accumulator
(1L)
Rotary compressor
(DA150A1F-21F)
Pressure
(psi)
Pd
Ps
Standard
416.2 145.0 2.87
Cooling
Overload
517.7 159.5 3.57
Low load
248.0 110.2 1.71
Standard
327.7
98.6 2.26
Heating
Overload
471.3 165.3 3.25
Low load
290.0
36.3 2.00
TO sensor
4-way valve
(STF-0213Z)
Muffler
Heat exchanger
Ø19.05 × 160L
Ø8 ripple, 2 rows, 20 stages
FP1.3, flat fin
Pipe surface temperature °F (°C)
(MPa)
Discharge
Suction
Pd
Ps
(TD)
(TS)
161.6
60.8
1.00
(72)
(16)
190.4
68
1.10
(88)
(20)
113.0
53.6
0.76
(45)
(12)
150.8
42.8
0.68
(66)
( 6)
172.4
68.0
1.14
(78)
(20)
172.4
–0.4
0.25
(78)
(–18)
(Pulse Motor Valve)
(CAM-B30YGTF-2)
TE sensor
Distributor
2-step muffler
Ø25 × 200L
Compressor
Indoor heat Outdoor heat
drive revolution
exchanger
exchanger
(TC)
(TE)
55.4
107.6
(13)
(42)
66.2
125.6
(19)
(52)
44.6
55.4
( 7)
(13)
98.6
37.4
(37)
( 3)
127.4
60.8
(53)
(16)
93.2
–0.4
(34)
(–18)
– 16 –
Revised : Feb. 2010
PMV
Muffler
Ø31.75 × 200L
Strainer
Refrigerant pipe
at liquid side Ø6.4
Packed valve
Refrigerant pipe
at gas side Ø12.7
Packed valve
In cooling operation
In heating operation
Indoor/Outdoor
temp. conditions
Indoor
(DB/WB) °F °C)
fan
frequency
(rps)
Indoor
80.6/66.2
58
HIGH
(27/19)
89.6/75.2
65
HIGH
(32/24)
64.4/59.9
30
LOW
(18/15.5)
68/–
64
HIGH
(20/–)
86/–
30
LOW
(30/–)
59/–
88
HIGH
(15/–)
Outdoor
95/–
(35/–)
109.4/–
(43/–)
23/–
(–5/–)
44.6/42.8
(7/6)
75.2/64.4
(24/18)
5/–
(–15/–)