Installation Instructions
Please Leave for Occupant
Package Contents and Part Identification
Control
Shaft
Control
Important Notes
Please Read Before Installation
Switchbox and Location: A single-gang switchbox (3"
high x 2" wide x 2
1
/
" deep) will service all individual Nova
2
dimmers. These dimmers are designed to operate in
ambient temperatures from 0
Allow a minimum space of 4
dimmer for proper heat dissipation.
Short Circuit Check: Check new installation for short
circuits prior to installing dimmer. With POWER OFF,
connect incoming neutral to the white wire, and the hot
wire to both ballast input wires (black wire with brown wire
or yellow/blue wire or orange wire, depending on ballast
used). Turn power ON. If lights do not work, or breaker
trips, a short is present. Correct the wiring and check
circuit again. Install dimmer only when short is no longer
present. This check should be done by a qualified
electrician.
Sockets: Use only with rapid start lamp sockets. Lamp
disconnect sockets may be required for use with certain
manufacturer's ballasts. This is in order to meet U.L. and
NEC regulations and maintains personal safety standards.
Lutron does not require lamp disconnect sockets with their
ballasts. Refer to the manufacturer's ballast label for this
information.
Lamps: Use only rapid start fluorescent lamps. Energy
Saver Lamps may NOT be used with this dimmer. With
magnetic ballasts only, do not mix different wattage
lamps in the same circuit. NOTE: For proper dimming
performance lamps must be operated at full intensity for
100 hours prior to dimming.
Ballasts: Use ONLY dimming ballasts listed on chart in
step 2 of Pre-Installation. With magnetic ballasts only, do
not mix 1 and 2 lamp ballasts in any one dimmer circuit. Do
not mix ballasts manufactured by more than one company.
Using single lamp ballasts will produce the most consistent
low end dimming level.
Multi-phased Applications (120/208-3 Phase): In multi-
phased applications use a separate neutral for each phase
containing a dimmer. Contact the Lutron Technical
Assistance Hotline toll-free for Application Note #17,
"Common Neutral Interaction".
Slider
Faceplate
Mounting
Screws
5 Wire
Connectors
Screwdriver
o
o
o
o
C (32
F) to 40
C (104
F).
1
/
" above and below the
2
Fluorescent Dimmers
NF-10, NF-20, NF-30
NF-10-277, NF-20-277
Pre-Installation
1.
Determine the number of dimmers to be ganged in the
same wallbox. If installing a single dimmer in a switchbox,
continue to the "Single Unit Installation" section on page 3.
2.
If more than one dimmer is being ganged in the same
wallbox, side sections can be removed to fit in existing
switchboxes. When controlling magnetic ballasts, breaking
side sections off the dimmer will reduce the maximum
number of lamps per dimmer. Use the following charts to
determine the maximum number of lamps per dimmer.
Figure A: Derating Ballast Chart
120V Applications
Number of Side Sections Removed
Magnetic
Ballasts
None
Controls
NF-10 NF-20 NF-30 NF-10 NF-20 NF-30 NF-10 NF-20 NF-30
Ballasts
Units listed are maximum number of LAMPS per control
Universal
550LTCP
12
24
36
502ATCP
*
12
24
36
Advance
DIM 140H
10
20
30
DIM 240H*
10
20
30
Valmont
8G5001W
12
24
36
8G5007W*
12
24
36
can be used with 30W lamps
* 2 lamp ballast
Electronic
Ballasts
NF-10**
Lutron
NF-10 controls when used with
Lutron electronic dimming
Hi-lume
16 Amps
ballasts do not require derating
Eco-10
when side sections are removed.
** Only NF-10 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
277V Applications
Number of Side Sections Removed
Magnetic
Ballasts
None
Controls
NF-10-277 NF-20-277 NF-10-277 NF-20-277 NF-10-277 NF-20-277
Ballasts
Units listed are maximum number of LAMPS per control
Magnetek
Universal
679LTCP
12
24
678LTCP
12
24
Electronic
Ballasts
NF-10-277**
Lutron
NF-10-277 controls when used
with Lutron electronic dimming
Hi-lume
8 Amps
ballasts do not require derating
Eco-10
when side sections are removed.
** Only NF-10-277 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
These products are covered under one or more of the following U.S. patents:
4,663,570; 4,894,587; 5,001,386; 5,041,763; 5,055,742; 5,173,643; 5,224,029 and
corresponding foreign patents. U.S. and foreign patents pending. Lutron, Hi-lume,
and Nova are registered trademarks and Eco-10 is a trademark of Lutron Electronics
Co., Inc.
1997 Lutron Electronics Co., Inc.
120VAC, 60Hz
277VAC, 60Hz
One
Two
9
22
34
6
19
31
9
20
32
4
18
28
7
18
27
4
15
25
6
18
26
4
14
24
9
22
34
6
19
31
9
20
32
4
18
28
One
Two
11
21
10
20
10
20
10
20
1

Advertisement

loading

Summary of Contents for Lutron Electronics Nova NF-10

  • Page 1 This is in order to meet U.L. and NEC regulations and maintains personal safety standards. ** Only NF-10 may be used with Lutron Ballasts. Total Amps are determined by Lutron does not require lamp disconnect sockets with their adding all ballast line currents as indicated on ballast label.
  • Page 2 Multi-gang Installation In multi-gang installations several dimmers or controls are Wire each dimmer according to Steps in "Single Unit grouped horizontally in one ganged switchbox or in a Installation" on page 3. series of interconnected switchboxes. Multi-gang faceplates are available to simplify and improve the Install dimmers in switchbox(es).
  • Page 3 Hold faceplate steady as you rub to keep a straight edge. See Figure H. Figure H: Cutting Faceplate Offset Mounting Holes Center Mounting Holes Turn power ON. Multigang faceplates, which eliminate the need to cut individual faceplates, are available from Lutron.
  • Page 4 Blue/White Warranty Blue * Lamp Lutron will, at its option, repair or replace any unit that is defective in materials or Disconnect manufacture within one year after purchase. For warranty service, return unit to place Socket of purchase or mail to LUTRON at 7200 Suter Road, Coopersburg, PA 18036-1299, Lamp postage prepaid.

This manual is also suitable for:

Novanf-20Nova nf-30Nova nf-10-277Nova nf-20-277Nova nf-20