Additional Remote Handsets calling Master Control Console Privacy and Conference Mode Ending Conversation 4. FAULT CONDITIONS 4.1. Silencing the Buzzer 4.2. Resetting the System 5. INDICATORS TEST 6. RECORDING MODULE (Optional) 7. MAINTENANCE AND TESTING APPENDIX A Operator’s Manual for Fireman Intercom PATENT...
System Description Premium PATENT Fireman Intercom System provides a two-way communication between remote areas and the Fire Command Centre in a building. The system comprises of a Master Control Console and Remote Handsets which are located at designated areas.
Privacy and Conference Mode. Each Zone Control Module controls and supervises 8 remote handsets. It is used to select and deselect the remote handsets as well as monitoring faults and calls from remote handsets. Operator’s Manual for Fireman Intercom PATENT...
The Supervisory Termination Panel is an interface between the Master Control Console and the Remote Handsets. Each panel can connect up to 8 handsets. This panel should not be opened unless for installation or maintenance purpose. Operator’s Manual for Fireman Intercom PATENT...
Raise the master handset from its cradle. This will allow the operator to select the remote handset(s). An audible tone will be produced in the master handset. This tone will disappear if any remote handset is raised. Operator’s Manual for Fireman Intercom PATENT...
Zone Control Module will disappear. Replacing the master handset back to its cradle when all remote handsets are hooked will make the Fireman Intercom System resume its normal operating condition. Operator’s Manual for Fireman Intercom...
8 of 10 FAULT CONDITIONS The Fireman Intercom System is designed to check itself and indicates a wide range of possible faults. In the event of a fault, the following will be observed: An amber led indication of the fault in question...
The Recording Module, together with a modified Cassette Recorder (TEAC W-790R), provides recording of conversation on the Fireman Intercom in the event of a fire alarm. The System Control Module has a digital counter (max 120 mins), which shows the time lapse of recording of each recording event.
As recommended by CP 25: 1999, Section 10, a combined monthly test of the fire alarm and the Fireman Intercom system should be carried out under simulated fire emergency conditions. The test should include the following operations: all visual and audible indicating devices at the fire command centre shall be checked;...
Remote Handset Fault -Wires connected to the remote -Check termination and condition of wires (Affected handset shown handset not terminated properly/ on Zone Control Module) defective -Components inside the remote -Call for service handset is damaged Operator’s Manual for Fireman Intercom PATENT...