DeDietrich GT 430 Service Manual page 9

Fuel oil/gas boilers
Table of Contents

Advertisement

3.2.3
Boilers for following countries: Switzerland
Maximum operating pressure: 6 bar
Boiler thermostat setting: 30 to 90°C
Boiler
Useful output
Power input
Number of sections
Water content
∆ T = 10K
(1)
∆ T = 15K
Water resistance
∆ T = 20K
Pressure in the
furnace for nozzle
(1)
pressure = 0
(1) (3)
Smoke temperature
Fuel oil
Mass flue gas flow
(1) (2) (4)
rate
Gas
Diameter,
combustion chamber
Width, combustion
chamber
Combustion chamber
Depth, combustion
chamber
Volume
Maintenance
∆ T = 50K
consumption*
Net weight
*Maintenance consumption: total heat emission when the burner is
off as a percentage of the nominal input power when the difference
between the mean boiler temperature and the room temperature is
50K.
(1)
Nominal operation (top boiler power)
In order for the boiler to operate correctly, it is imperative
to respect the draught at the nozzle.
)
(2
CO
= 13% on fuel oil and 9% on natural gas
2
(3)
Ambient temperature : 20 °C
(4)
in accordance with DIN 4705 Teil 1
03/12/07 - 300011893-001-B
Maximum operating temperature: 120°C
Safety thermostat: 110°C
GT 430-8
GT 430-9
kW
180-224
212-264
kW
196-244
231-287
8
9
l
366
409
10
16
mbar
6
9
3
4
mbar
0.3
0.45
°C
160
160
373
439
Kg/h
410
483
mm
530
530
mm
638
638
mm
1183
1343
3
0.310
0.354
m
%
0.2
0.17
kg
1802
2072
GT 430
GT 410-10
GT 430-11
GT 430-12
252-312
305-400
365-470
274-340
332-435
397-511
10
11
452
495
26
44
14
20
7
12
0.6
0.8
160
170
520
665
572
732
530
530
638
638
1503
1663
1823
0.396
0.439
0.481
0.16
0.12
2238
2454
2638
1 mbar = 10 mmCE = 10 daPa
GT 430-13
GT 430-14
425-530
475-580
462-576
517-631
12
13
14
538
581
624
63
84
103
28
37
48
16
21
25
1.1
1.3
1.5
170
170
170
781
880
963
860
969
1061
530
530
530
638
638
638
1983
2143
0.523
0.565
0.11
0.11
0.10
2880
3057
9