Outlines And Dimensions - Mitsubishi Electric PLA-RP·BA(2) Technical Data Book

Split-type, heat pump air conditioners.
Hide thumbs

Advertisement

3

OUTLINES AND DIMENSIONS

INDOOR UNIT
PLA-RP35BA
PLA-RP50BA
PLA-RP71BA2
PLA-RP100BA2 PLA-RP125BA2
20~45
Fresh air
intake hole
160
Remote controller
terminal block
Branch duct hole
187.5
Suspension bolt
M10 or W3/8
1
60
2
Suspension bolt
lower edge
Control wire entry
M
Air intake grille
M
Indoor unit
Ceiling
3000mm or more
Grille
Obstacle
1500mm
or more
Floor
PLA-RP60BA
Ceiling hole
20~45
860~910
810
Suspension bolt pitch
Indoor unit/Outdoor unit
connecting terminal block
Indoor power supply
terminal block(Option part)
160
840
284
377
Power supply wire,
Ceiling
Indoor unit/Outdoor unit
connecting wire entry
Grille
597
Air intake hole
Drain hole
Drain pump clean hole
and Drain emergency
drainage hole
M
M
500
83
36
Air outlet hole
950
Indoor unit
1800mm or more
from floor
For high
attachment
PLA-RP100BA
Detail connecting of branch duct(Both aspects)
Branch duct hole
(
Connected the attached
Drain pipe
connected to VP-25
flexible pipe or socket.
Keep approximately
10 to 15mm space
between unit ceiling
and ceiling slab.
In case of standard grille : PLP-6BA / PLP-6BAMD
In case of Auto-Grille : PLP-6BAJ
In case of wireless remote controller : PLP-6BALM
Emergency operation
Auto vane
switch<Cooling>and
(Air outlet)
Emergency Up/Down switch<Up>
Emergency operation
switch<Heating>and
Emergency Up/Down switch<Down>
DEFROST/STAND BY lamp
Receiver
Operation lamp
Vane motor
Note 1. Please choose the Grille from a standard grille or Auto-Grille.
2. As for drain pipe, please use VP-25(O.D. 32 PVC TUBE).
Drain pump is included.
Max. lifting height is 850mm from the ceiling.
3. As for suspension bolt, please use M10 or W3/8. (Procured at local site)
4. Electrical box may be removed for the service purpose.
Make sure to slack the electrical wire little bit for control/ power wires connection.
5. The height of the indoor unit is able to be adjusted with the grille attached.
6. For the installation of the optional high efficiency filter or optional multi-functional casement.
1) Requires E or more space between transom and ceiling for the installation.
2) Add 135 mm to the dimensions marked on the figure.
3) The optional high efficiency filter becomes optional multi-functional casement and concomitant use.
7. When installing the branch ducts, be sure to insulate adequately.
Otherwise condensation and dripping may occur. (It becomes the cause of dew drops/water dew.)
8. As for necessary installation/service space, please refer to the left figure.
Models
1
PLA-RP35/50BA
Refrigerant pipe
··· 6.35
Flared connection
···1/4 inch
Refrigerant pipe
PLA-RP60BA
6.35 /
9.52
Flared connection
1/4 inch / 3/8 inch
(compatible)
PLA-RP71BA
Refrigerant pipe
PLA-RP71BA2
··· 9.52
Flared connection
PLA-RP100,125,140BA
···3/8 inch
PLA-RP100,125BA2
10
PLA-RP125BA
90
100
100
90
350
175
Burring hole pitch
150
Cut out hole
Detail drawing of fresh air intake hole
Burring hole
Burring hole pitch
3- 2.8
125
)
Cut out hole
100
Ceiling
Auto Grille
Air intake grille up/down discharge
L.L Filter
Air intake grille
A
B
C
2
Refrigerant pipe
··· 12.7
80
Flared connection
···1/2 inch
74
241 258
87
Refrigerant pipe
··· 15.88
Flared connection
···5/8 inch
85 77
281
298
Unit : mm
Cut out hole
14- 2.8
Burring hole
Ceiling
D
E
400
440