3. Example of safety system configuration

Example 1
START
Emergency stop button
+24V
X0
COM0
X1
Internal
DC24V
Safety
Circuit
24G
MITSUBISHI MELSEC Safety relay module
QS90SR2SN-Q
Fig.3 Safety system example 1 – STOP asynchronous with emergency stop button and fault
For safety stop, configure the wiring as shown in Fig.3 above.
Note: the above wiring is configured to prevent restart in case of a fault.
The parameter No.192 (A,B,C terminal function selection) must be set to '81'. This setting makes the A-C
output to open in case of failure.
After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.
In the above configuration, after reset of emergency stop button, drive will be in safe-state until START
switch is pressed.
To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.
STF
STOP
COM1
XS0
XS1
Z00
Z10
Z20
K1
K2
Z01
Z11
Z21
detection through A-C output.
A(SAFE2)
B
RY
C
STF
STOP
PC
SOURCE
+24V
S1
+24V
S2
SC
CAUTION
5
CPU
Gate
Gate
Driver
Driver
G
G
FR-D700
T
IGBTs
W
IM

Advertisement

loading