6. APPENDIX

6.4 Cable specification

1.
Single phase unit
Nameplate
maximum
Phase line
current
No more
2 1.5mm
than 13A
13~25A
2 4mm
25~30A
2 6mm
30~40A
2 10mm
40~55A
2 16mm
55~70A
2 25mm
2. Three
phase unit
Nameplate
maximum
Phase line
current
No more
3 1.5mm
than 13A
13~25A
3 4mm
2
25~30A
3 6mm
2
30~40A
2
3 10mm
40~55A
2
3 16mm
55~70A
2
3 25mm
When the unit will be installed at outdoor, please use the cable which can against UV.
MCB
Earth line
2
2
1.5mm
20A
2
1.5mm
40A
2
2
4mm
40A
2
2
63A
6mm
2
2
80A
10mm
2
2
16mm
100A
2
Neutral line
Earth line
2
2
2
1.5mm
1.5mm
2
2
4mm
1.5mm
2
2
4mm
4mm
2
6 mm
2
4mm
2
10 mm
2
4mm
16 mm
2
2
4mm
24
Creepage protector
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
30mA less than 0.1 sec
Creepage protector
MCB
30mA less than 0.1 sec
20A
40A
30mA less than 0.1 sec
30mA less than 0.1 sec
40A
63A
30mA less than 0.1 sec
80A
30mA less than 0.1 sec
100A
30mA less than 0.1 sec
Signal line
2
n 0.5mm
Signal line
2
n 0.5mm