SANTA FE INSTALLER'S AND OWNER'S MANUAL 2.1D In A Remote Area, Duct Outlet Only. 2.4 Ducting A simpler remote installation method than above uses ducting 2.4A Optional Ducting between the Santa Fe discharge and the humid room; the An inlet shroud with an 8” round collar and an 8” round Santa Fe inlet draws air from the room in which it’s located.
SANTA FE INSTALLER'S AND OWNER'S MANUAL If dirty, the foam pre-filter can be vacuumed or carefully hand and condensed by giving up its heat to the air that is about to washed with warm water and mild detergent, then rinsed. The be discharged from the unit.
SANTA FE INSTALLER'S AND OWNER'S MANUAL 5.4 Refrigerant Charging 5. Compressor terminals C and R: No continuity indicates If the refrigerant charge is lost due to service or a leak, a new an open run winding. The compressor must be replaced. charge must be accurately weighed in.
SANTA FE INSTALLER'S AND OWNER'S MANUAL 5.8 Defrost Thermostat has some light carbon deposits, the burn out occurred while the compressor was not rotating. Contaminants are The defrost thermostat is attached to the refrigerant therefore largely confined to the compressor housing. A suction tube between the accumulator and compressor.
SANTA FE SERVICE PARTS LIST • To order contact your reseller or call 1-800-533-7533 ITEM PART NO. QTY. DESCRIPTION 4022254 Accumulator 4021475 Air Filter, Pleated, 2” x 16” x 20” 4021468 Air Filter, Foam Element 4022037 Blower w/ Capacitor 4021589 Capillary Tubes, .050” ID x 28” long 4023474 Compressor, Panasonic (2R12S3R126A-6A) 4022144...
SANTA FE OPTIONAL REMOTE HUMIDITY CONTROL CAUTION This should only be performed by a qualified electrician. A 120Vac remote humidity control is available from the factory. This replaces the factory mounted humidity control on the cabinet of the dehumidifier, and allows the unit to accurately sense the humidity in an area other than the one where the unit is located.
SANTA FE CONDENSATE PUMP INSTALLATION INSTRUCTIONS STEP 1: The condensate pump kit STEP 2: Pre-drilled mounting holes are located STEP 3: Secure the condensate pump to the includes: drain hose, condensate pump, two near the bottom and on the same side of the unit with the two provided screws.
SANTA FE DUCTABLE INLET MOUNTING Ductable Inlet Instructions Exhaust Collar Mounting Instructions 1. Remove the Filters from the unit. 5. The six inch opening may be used as a fresh air inlet from outside. 2. Remove the ductable inlet from the box and remove the release paper from the tape on the inlet flanges.
SANTA FE MUFFLER KIT INSTRUCTIONS Component List On the Santa Fe, the muffler kit and (1) Silencer condensate pump kit may be used (1) #8-18 Screw together, but the pump will not be (1) Instructions able to be mounted to the unit. Note: Washer and (2) screws are not used on the Santa Fe.
SANTA FE FILTER INSTALLATION INSTRUCTIONS Instructions: To prevent damaging the foam filter, place it “grid side up” on top of the pleated filter and slide them both into the filter slot. Foam filter with Pleated filter with plastic grid up air flow arrow pointed down FLOW...
APPLICABLE TO THE SANTA FE DEHUMIDIFIER OR will operate free from any defects in materials and ANY PART THEREOF, ALL OTHER WARRANTIES workmanship, or Therma-Stor LLC will, at its option, IMPLIED BY LAW, INCLUDING MERCHANTABILITY repair or replace the defective part(s), free of any AND FITNESS FOR A PARTICULAR PURPOSE, charge.