SL1100
• Up to 12 System Alarm times can be scheduled to print on a Monthly, Daily, and Hourly time frame.
The report indicates both Major and Minor Alarms.
• System Information Reports cannot be set to output at a scheduled time.
• When using the E-mail functionality of reports, the E-mail address in PRG 90-11-10 (From Address)
must be set for the E-mail feature to work.
• After a new alarm is output, it cannot be output a second time. New alarms must be generated
before PRG 90-12-04 can be performed a second time.
• Up to 100 System Alarm Reports can be stored. When the buffer fills, the oldest record is deleted to
allow the new record to be saved.
• If the System is set up to E-mail the Alarm Reports and the Mail Server is down, the report is not
sent.
• System Information Reports cannot be set for output via E-mail.
• Scheduled Alarm Reports via E-mail prints all alarms. When the system detects New alarms, this
A
information is output via E-mail individually.
• E-mail Alarm Reports can be sent when each new alarm occurs (Per Event). If you want to receive
complete Alarm Reports periodically, you must specify 12 individual dates and times in PRG
90-24-01 ~ PRG 90-24-04 (per period).
A maximum of 99 entries are emailed with the scheduled alarms.
• System Alarm Report can be sent by E-mail using following features. (V2.0 or higher)
In case of the PRG 90-11 SMTP client notifies of an alarm report in the email text.
In case of the PRG 47-18 SMTP client attaches an alarm report to an email as a text file and
notifies. MEMDB/InMailCF mounting is required.
- PRG 47-18: Set to SMTP server setting (Outside E-mail service is necessary)
- PRG 90-11-14: Set YES to use PRG 47-18 SMTP client.
In case of No uses a PRG90-11 SMTP client.
- PRG 90-11-15: Set YES to transmit DIMLAST, DIMDUMP. PRG 90-11-14=YES (PRG 47-18
SMTP Client uses) is necessary .
- Alarm Report per event
When an alarm occurs, an alarm report will be sent by E-mail.
• PRG 90-10-02 System Alarm Setup - Report = 1: Yes
• PRG 90-11-02 System Alarm Report Setup - Report Method = 1: E-mail
- Alarm Report per period
According to the PRG 90-24 (Alarm Report Notification Time Setup), an alarm report will be sent
by E-mail.
- DIMLAST/DIMDUMP Notification
If PRG 90-11-15 is On, Dimlast.gz and Dimdump.gz will be sent by E-Mail when system failed.
- When the E-mail transmission failed
When failed the E-Mail transmission, the retry process will be started (15 minutes x 95 times)
• An attached Text File will be saved to the InMail CF temporary until the e-mail transmission is
completed. (V2.0 or higher)
The maximum 200 files can be saved to the InMail CF temporary.
• The Text File in the InMail CF will be deleted when the e-mail transmission is completed. (V2.0 or
higher)
• When the E-Mail Transmission is failed and maximum retry process (15 min x 95 times) is over, the
E-mail and attached text file will be deleted. (V2.0 or higher)
• When the maximum SMTP client Mail Buffer capacity (200) is over, an alarm report does not send.
(V2.0 or higher)
Default Settings
None
1-28
ISSUE 2.0
Alarm Reports