Service and Adjustment
(cont'd)
L.R Gas Control Valve & Burner
Assembly Replacement
Information
Draining
The water heater should be drained if being shut down during
freezing
temperatures.
Also periodic
draining
and cleaning
of
sediment
from the tank may be necessary.
AWARNING
PROPANE (L.R) GAS CONTROL VALVE AN BURNEI
ASSEMBLYREPLACEMENT INFORMATION.
For Propane (L.R) Gas Models Only:
Your water heater is equipped with a Propane (LR) gas con
trol valve and a main burner assembly with left hand threads
for the following fittings and their connections.
The connection
between the manifold and the gas
control valve (A to B) are left hand threads.
The connection
between
the main burner
orifice
and the manifold
(C to D) are left hand threads.
For ordering
these replacement
parts, please refer to
the "Repair
Parts" section of this manual.
A
Turn the gas control knob to the "OFF" position.
CLOSE the cold water inlet valve to the water heater.
OPEN a nearby hot water faucet and leave open to allow for
draining.
Connect a hose to the drain valve and terminate to an ade-
quate drain.
OPEN the water heater drain valve to allow for tank draining.
NOTE: If the water heater is going to be shut down and
drained for an extended period, the drain valve should be
left open with hose connected allowing water to terminate
to an adequate drain.
Close the cirain valve.
Follow instructions in the "Filling The Water Heater" section.
Follow the lighting instructions in the "Lighting" section to
restart the water heater.
Temperature-Pressure
Relief
Valve Operation
The temperature-pressure rehefvalve must be manually operated
at least once a year.
TEMPERATURE-PRESSURE
RELIEF VALVE
DISCHARGE
PIPE
Failure to install and maintain a new properly listed tempera-
ture-pressure relief valve will release the manufacturer from any
claim which might result from excessivetemperature or pressure.
AWARNING
If the temperature-pressure relief valve on the appliance
weepsor discharges periodically, this may be due to thermal
expansion. Your water heater may have a check valve
installed in the water line or a water meter with a check
valve. Consultthe SearsServiceCenter for further informa-
tion. Do not plugthe temperature-pressure relief valve.
AWARNING
When checking the temperature-pressure relief valve opera-
tion, make sure that (I) no one is in front of or around the
outlet of the temperature-pressure relief valve discharge line,
and (2) that the water manually discharged will not cause any
property damage because the water may be extremely hot.
If after manually operating the valve, it fails to completely
reset and continues to release water, immediately close the
cold water inlet to the water heater, follow the draining
instructions, and replace the temperature-pressure
relief
valve with a new one.