10.3.5. OUTDOOR UNIT ELECTRICAL
WIRING
1. Remove Top Panel.
2. Remove Control Board Cover.
3. Remove Plugs.
4. Fix the conduit connectors to the conduit holes with lock-
nuts, then secure them.
5. Connecting wire between indoor unit and outdoor unit
should be UL listed or CSA approved 4 × AWG16 wire.

10.3.6. PIPE INSULATION

1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap
the insulated piping end to prevent water from going inside the piping.
2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM
with thickness 6 mm or above.
CHECK THE DRAINAGE
• Open front panel and remove air filters.
(Drainage checking can be carried out without removing the
front grille.)
• Pour a glass of water into the drain tray-styrofoam.
• Ensure that water flows out from drain hose of the indoor
unit.
6. Secure the wire onto the control board with the holder
(clamper).
7. Wire connection to the power supply (208/230V 60 Hz)
through circuit breaker.
• Connect the UL listed or CSA approved wires (AWG12)
to the terminal board, and connect the other end of the
wires to circuit breaker.
Note: Secure the wires onto the control board
with the holder (clamper).
8. After completing wiring connection, reattach the control
board cover and the top panel to the original position with
the screws.
EVALUATION OF THE PERFORMANCE
• Operate the unit at cooling operation mode for fifteen
minutes or more.
• Measure the temperature of the intake and discharge air.
• Ensure the difference between the intake temperature and
the discharge is more than 14.4°F.
CHECK ITEMS
Is there any gas leakage at flare nut connections?
Has the heat insulation been carried out at flare nut
connection?
Is the connecting cable being fixed to terminal board firmly?
Is the connecting cable being clamped firmly?
Is the drainage OK?
(Refer to "Check the drainage" section)
Is the earth wire connection properly done?
Is the indoor unit properly hooked to the installation plate?
Is the power supply voltage complied with rated value?
Is there any abnormal sound?
Is the cooling operation normal?
Is the thermostat operation normal?
Is the remote control's LCD operation normal?
Is the air purifying filter is installed?