Outdoor Unit; Connecting The Piping - Panasonic CS-C18DKU Service Manual

Hide thumbs Also See for CS-C18DKU:
Table of Contents

Advertisement

CS-C18DKU CU-C18DKU / CS-C24DKU CU-C24DKU

10.3. Outdoor Unit

10.3.1. SELECT THE BEST LOCATION
(Refer to "Select the best location" section)
10.3.2. INSTALL THE OUTDOOR UNIT
• After selecting the best location, start installation according
to Indoor/Outdoor Unit Installation Diagram.
1. Fix the unit on concrete or rigid frame firmly and horizontally
by bolt nut. (ø13/32").
2. When installing at roof, please consider strong wind and
earthquake. Please fasten the installation stand firmly with
bolt or nails.

10.3.3. CONNECTING THE PIPING

Connecting The Piping To Indoor Unit
Please make flare after inserting flare nut (locate at joint portion
of tube assembly) onto the copper pipe. (In case of using long
piping)
Connect the piping
• Align the center of piping and sufficiently tighten the flare
nut with fingers.
• Further tighten the flare nut with torque wrench in specified
torque as stated in the table.
MODEL
C18DK
C24DK
Connecting The Piping To Outdoor Unit
Decide piping length and then cut by using pipe cutter.
Remove burrs from cut edge. Make flare after inserting the
flare nut (located at valve) onto the copper pipe.
Align center of piping to valves and then tighten with torque
wrench to the specified torque as stated in the table.
CUTTING AND FLARING THE PIPING
1. Please cut using pipe cutter and then remove the burrs.
2. Remove the burrs by using reamer. If burrs is not
removed, gas leakage may be caused.
Turn the piping end down to avoid the metal powder
entering the pipe.
3. Please make flare after inserting the flare nut onto the
copper pipes.
42
Piping size (Torque)
Gas
Liquid
1/2" (40.6 lbf. ft)
1/4" (13.3 lbf. ft)
5/8" (47.9 lbf. ft)
1/4" (13.3 lbf. ft)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu-c18dkuCs-c24dkuCu-c24dku

Table of Contents