SERVICING PRECAUTIONS

Features of refrigerant (R600a)
• Achromatic and odor less gas.
• Flammable gas and the ignition (explosion) at 494°C.
• Upper/lower explosion limit: 1.8%~8.4%/Vol.
Features of the R600a refrigerator
• Charging of 60% refrigerant compared with a R134a model.
• The suction pressure is below 1bar (abs) during the operation.
• Because of its low suction pressure, the external air may flow
in the cycle system when the refrigerant leak, and it causes
malfunction in the compressor.
• The displacement of compressor using R600a must be at
least 1.7 times larger than that of R134a.
• Any type of dryer is applicable (XH-5, 7, 9).
• The EVAPORATOR or any other cycle part that has welding
joint is hidden in the foam. (If not hidden inside, the whole
electric parts must be tested with the LEAKAGE TEST
according to the IEC Standard.)
• The compressor has label of the refrigerant R600a.
• Only the SVC man must have an access to the system.
Installation place
• Must be well ventilated.
• Must be 20 m
3
or larger.
• Must be no-smoking area.
• No ignitable factors must be present.
Utilities
• Refrigerant cylinder (MAX NET 300g)
• Manometer
• Vacuum pump (600
/min)
• Piercing Clamp
• Quick coupler
• Hoses (5m-1EA, 1m-3EA)
• LOKRING
• Portable Leakage detector (3g/year
• Nitrogen cylinder (for leakage test)
• Concentration gauge
Make sure before Servicing
• Refrigerant
Confirm the refrigerant by checking Name Plate and the label
on the compressor, after opening the COVER ASSEMBLY,
BACK-M/C.
• If the refrigerant is R600a, you must not weld or apply a heat
source.
Air Recharging in Compressor
Before refilling the refrigerant, you must perform the test
according to Chapter 5 (TROUBLESHOOTING CHART). When
the defects are found, you must discharge the residual
refrigerant (R600a) in the outdoor. For discharging the
refrigerant R600a, break the narrow portion of tube extension
by hand or with a pipe cutter as shown in Figure 1. Leave it for
30min in outside to stabilize the pressure with ambient. Then,
check the pressure by piercing the dryer part with piercing
pliers. If the refrigerant is not completely discharged, let the
refrigerator alone for more 30min in outside.
Figure 1
Attach the service tube installed with a Schrader valve (one-
way valve) by using the LOKRING (Figure 2). Then, connect
the Schrader valve (one-way valve) to the pump that is
connected to the discharging hose leading to the outside.
When discharging the residual refrigerant, repeat 3 cycle that
includes 3min of the pump running->pump off->30sec of the
compressor running.
)
Figure 2
- 3 -
After the refrigerant (R600a) is completely discharged, repair
any defective parts and replace the dryer. At any case you
must use the LOKRING for connecting or replacing any part in
the cycle (No Fire, No Welding). Connect the Schrader valve
to pump with the coupler. And then turn the pump on for
vacuum state (Figure 3). Let the pump run until the low-
pressure gauge indicates the vacuum (gauge pressure 0,
absolute pressure -1atm or -760mmHg). Recommended
vacuum time is 30 min. Charge the N
leakage from welding points and the LOKRING. If leakages
are found, repair the defects and repeat the vacuum process.
Figure 3
After the system is completely vacuumed, fill it with the
refrigerant R600a up to what has been specified at your
refrigerator Name Plate. The amount of refrigerant (R600a)
must be precisely measured within the error of ±2g by an
electron scale (Figure 4).
If you use the manifold connected with both the refrigerant
(R600a) cylinder and the vacuum pump simultaneously, make
sure the pump valve is closed (Figure 5).
Figure 4
Connect the charging hose (that is connected to the
refrigerant (R600a) cylinder) to the Schrader valve installed
on the service tube. Then, charge the refrigerant (R600a) by
controlling the Throttle valve. When you do so, do not fully
open the Throttle valve because it may make damage to the
compressor. Gradually charge the refrigerant (R600a) by
changing open and close the Throttle Valve (5g at each time).
The charging hose must use a one-way valve to prevent the
refrigerant refluence. Close the Schrader valve cap after the
refrigerant (R600a) is completely recharged.
After you completely recharge the refrigerant (R600a),
perform the leakage test by using a portable leakage detector
or soapy water. Test the low pressure (suction) parts in
compressor off time and high pressure parts in compressor
on time. If the leakages are found, restart from the refrigerant
(R600a) discharging process and repairs defects of leaks.
After the leakage test, check the temperature of each parts of
the cycle. Check with hands if the CONDENSER and the
case (HOT-LINE pipe) that is contacted to the door gasket
are warm. Confirm that frost is uniform distributed on the
surface of the EVAPORATOR.
gas in order to check for
2
Figure 5