Operating Instructions
RDG100T/H – the electronic room thermostat that allows you to set the ideal room temperature you
want. The thermostat provides Comfort, Energy saving mode and Protection mode and, in addition, an
Auto Timer mode with 8 programmable timers. The fan operates either in Automatic mode or at the
selected speed when using Manual mode. You can either rely on the factory settings or make adjust-
ments that suit your individual needs.
Main display
Room temperature
Room temperature in degrees Celsius
Room temperature in degrees Fahrenheit
Button lock active
Alert indicator
Condensation in the room
Temporary timer function active
Weekday
1 = Monday
7 = Sunday
Setting time and weekday
Setting the auto timers
Current time of day
Escape (Cancel)
Confirmation (OK)
Changing the room temperature
The room temperature setpoint can be adjusted with the rotary knob when Comfort
mode
is active or with
Turn the rotary knob clockwise (+) to increase, or counterclockwise (-) to decrease the
current room temperature setpoint for Comfort mode
The setting range is from 5...40 °C, unless limited by parameters P09 and P10 (for parameter settings,
see reverse side).
Adjusting the fan speed
Press the fan mode button until the desired fan mode is reached
In Automatic mode
, the fan speed is automatically selected by the thermostat
depending on the setpoint and the actual room temperature. When the room tem-
perature reaches the setpoint, the fan stops (factory setting) or keeps running at low
speed (P15).
In Manual mode, the fan operates independently and always runs at the same speed:
Low
Low / medium / high
Medium
Note:
If desired, you can change the fan mode selector option via P03: Manually only, or manually
High
including Protection mode. Use P15 to adjust the fan speed in dead zone.
Changing from heating to cooling mode
Depending on the type of plant, the changeover from heating to cooling (or vice
versa) is made either automatically by a changeover sensor or a remote changeover
switch, or manually by pressing the operating mode button (see parameter P01)
To select cooling or heating manually (P01=2), press the operating mode button until
the desired mode appears
With automatic changeover or continuous heating / cooling, symbols
that the system currently operates in heating or cooling mode
With manual changeover, symbol appears, indicating that the system currently
operates in heating or cooling mode
Changing the operating mode
Press the operating mode button until symbol appears, indicating that Protection /
Comfort / Auto Timer / Energy Saving mode is selected.
1. Protection mode
In protection mode, the plant stops operating. If the room temperature falls below
8 °C, heating is switched on however to protect the room against frost
The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer:
Frost protection: _________ ˚C
2. Comfort mode
In Comfort mode, the thermostat maintains the setpoint which can be readjusted with
the rotary knob
3. Auto Timer mode
In Auto Timer mode, the controller automatically switches over between Comfort
and Energy Saving mode according to the 8 preprogrammed timers
4. Energy Saving mode
When selecting Energy Saving mode, make sure that parameter P02 is set to 2
In Energy Saving mode, the room temperature is maintained at a lower or higher
setpoint, thus saving energy and money! You can change the preselected setpoint by
adjusting parameters P11 and P12 (for parameter settings, see reverse side)
Important: The setpoint for Energy Saving mode can be set to OFF. This means that the thermostat is
deactivated! Risk of frost, i.e. no protective heating or cooling function is provided!
Setting the time of day and the weekday
1. Press the program mode button for programming.
2. Press button
(OK) to enter the setting mode for the time of day.
3. The time digits start blinking. Turn the rotary knob clockwise or counterclockwise to set the time of
day.
If the current time of day is in 24-hour format and you wish to change it to the 12-hour format, turn
the knob clockwise passed 23:59 or counterclockwise passed 00:00. Vice versa back to the 24-hour
format.
4. Confirm the time of day by pressing button
5. Turn the rotary knob clockwise or counterclockwise to set the current weekday.
6. Confirm the current weekday by pressing button
7. Press button
(Esc) to leave the program mode.
Note:
After a power failure, the time of day starts blinking to indicate power was lost. However, the auto timer continues to
run with the time before the power failure occurred. Select the setting mode to readjust the time if needed.
RDG100T/H
Operating mode button
Program mode button
Fan mode button
Rotary knob
Operating mode
Heating mode
Electric heater on
Cooling mode
Comfort mode
Energy Saving mode
Auto timer
Protection mode: Protection against frost
Indicator for selecting mode
Fan mode
Automatic
Manual
Low
Medium
High
/
indicate
Heat protection: __________˚C
and the weekday indicator starts blinking.
(OK).

Advertisement

loading

Summary of Contents for Siemens RDG100T

  • Page 1 Operating Instructions RDG100T/H RDG100T/H – the electronic room thermostat that allows you to set the ideal room temperature you want. The thermostat provides Comfort, Energy saving mode and Protection mode and, in addition, an Auto Timer mode with 8 programmable timers. The fan operates either in Automatic mode or at the selected speed when using Manual mode.