Safety; Sensepoint Xcd Technical Manual Spxcdhmanen Issue - Honeywell Sensepoint XCD Technical Manual

Gas detector
Hide thumbs Also See for Sensepoint XCD:
Table of Contents

Advertisement

Sensepoint XCD Technical Manual

1 Safety

Ensure that this Operating Manual is read and understood BEFORE installing / operating /
maintaining the equipment. Pay particular attention to Warnings and Cautions. All document
Warnings are listed here and repeated where appropriate at the start of the relevant chapter(s) of
this Operating Manual. Cautions appear in the sections/sub-sections of the document where they
apply.
Sensepoint XCD is designed for installation and use in Zone 1 or 2 hazardous areas in
many countries including Europe and for Class 1 Division 1 or 2 area applications in North
Installation must be in accordance with the recognized standards of the appropriate
Access to the interior of the detector, when carrying out any work, must only be conducted
Before carrying out any work ensure local regulations and site procedures are followed.
Appropriate standards must be followed to maintain the overall certification of the detector.
For installations where conduit is used, and the sensor is mounted directly to the
Sensepoint XCD, there must be a "Seal Fitting" installed for each of the cable gland entries
within 18 inches of the Sensepoint XCD. The total distance of the location of these Seal
Fittings is 18 inches. (e.g. If all 3 gland entries are to be used, 3 Seal Fittings should be
If using an anti-seize compound, the threads should be thinly coated with an approved
To reduce the risk of ignition of hazardous atmosphere, de-classify the area or disconnect
the equipment from the supply circuit before opening the detector enclosure. Keep
Never attempt to open a junction box/enclosure or replace/refit the sensor in potentially
hazardous atmospheres while power is still applied to the transmitter.
The detector must be earthed/grounded for electrical safety and to limit the effects of radio
frequency interference. Earth/ground points are provided inside and outside the unit. The
internal grounding shall be used as the primary equipment ground. The external terminal is
only a supplemental bonding connection where local authorities permit or require such a
Ensure that all screens/instrument earth/clean earth wiring is earthed/grounded at a single
point (either at the controller or detector - BUT NOT BOTH) to prevent false readings or
alarms that may occur due to potential earth/ground loops.
Take care when handling sensors as they may contain corrosive solutions.
Do not tamper with or in any way disassemble the sensor.
Do not expose to temperatures outside the recommended ranges.
Do not expose sensors under storage conditions to organic solvents or flammable liquids.
At the end of their working life, replacement electrochemical sensors for oxygen and toxic
gas must be disposed of in an environmentally safe manner. Disposal should be according
to local waste management requirements and environmental legislation.
Alternatively, old replaceable sensors may be securely packaged and returned to Honeywell
Electrochemical sensors should NOT be incinerated as this action may cause the cell to
Refer to the local or national regulations relative to the installation at the site. For Europe
This equipment is designed and constructed as to prevent ignition sources arising, even in
the event of frequent disturbances or equipment operating faults.
NOTE: The control card must have a suitably rated fuse.
WARNINGS
authority in the country concerned.
by trained personnel.
located, each within 6 inches of the wiring entrance).
silicone free compound e.g. petroleum jelly
assembly tightly closed during operation.
connection.
Analytics clearly marked for environmental disposal.
emit toxic fumes.
see EN60079-29-2, EN60079-14 and EN61241-14.
Only assessed for ATEX for ignition hazards.
America.
2
SPXCDHMANEN Issue 2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents