Protective Function

Canceling trip

First remove the cause and then reset the system by following one of the following steps.
[1] Turn off the inverter. Wait until the trip message disappears and then power
on again.
[2] Leaving the trip message displayed, connect both [I1] and [I2] to [G] for at
least 0.1 seconds.
[3] Leaving the trip message displayed, press both △ and ▽
on the operation panel for at least 1 second.
[4] Leaving the trip message displayed, issue the trip reset command.
* If the CPU error
procedure. The trip cannot be canceled with the above [2], [3] and [4] methods.
∗1
When [
I1/I2 function selection] is set to "I1: Run/stop" and "I2: CCW/CW", the trip cannot be
canceled.
∗2
This method is effective only when [
to
.
∗1
occurs, cancel the trip according to the above
I5 function selection] or [
-
-
36
switches
∗2
I6 function selection] are set