Operation; Function Of Controls - LG S092CG N40 Service Manual

Room air conditioner
Hide thumbs Also See for S092CG N40:
Table of Contents

Advertisement

Operation

Function of Controls

• DISPLAY
1) C/O Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Comp. Running Incidator
• While in appliance operation, ON while in outdoor unit compressor running, OFF while in compressor off.
2) H/P Model
Operation Indicator
• ON while in appliance operation, OFF while in appliance pause.
• Flashing while in disconnection or short in Thermistor. (3 sec off / 0.5 sec on)
Timer Indicator
• ON while in timer mode (on/off), OFF when timer mode is completed or canceled.
Defrost Indicator
• OFF except when hot start during heating mode operation or while in defrost control.
Cooling Mode Operation
• When the intake air temperature reaches 0.5°C below the setting temp, the compressor and the outdoor fan
stop.
• When it reaches 0.5°C above the setting temp, they start to operate again.
Compressor ON Temp
Compressor OFF Temp
• While in compressor running, operating with the airflow speed set by the remote control. While in compressor
not running, operating with the low airflow speed regardless of the setting.
Healthy Dehumidification Mode
• When the dehumidification operation input by the remote control is received, the intake air temperature is
detected and the setting temp is automatically set according to the intake air temperature.
26°C ≤ Intake Air Temp
24°C ≤ Intake Air Temp<26°C
18°C ≤ Intake Air Temp<24°C
Intake Air Temp<18°C
Setting Temp+0.5°C
Setting Temp-0.5°C
25°C
Intake Air Temp-1°C
Intake Air Temp-0.5°C
18°C
Operation
Service Manual 31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents