Functional Specifications BACnet Gateway

Monitoring and Controlling point of indoor and ventilator

Applicable monitoring and controlling point for the indoor and ventilator are listed below.
Object Name's XX is indoor's address number.
Name
1
ON/OFF (setting)
2
ON/OFF (status)
3
Lock (setting)
4
Lock (status)
5
Filter Sign
6
Filter Sign reset
7
Operation Mode (setting)
8
Operation Mode (status)
9
Swing (setting)
10
Swing (status)
11
Fan speed (setting)
12
Fan speed (status)
13
Set Room Temperature
14
Room Temperature
15
Alarm
16
Error Code
17
User Mode(setting)
18
User Mode(status)
44 BACnet Gateway
Object Name
StartStopCommand_XX
StartStopStatus_XX
LockCommand_XX
LockStatus_XX
FilterSign_XX
FilterSignReset_XX
ModeCommand_XX
ModeStatus_XX
SwingCommand_XX
SwingStatus_XX
FanSpeedCommand_XX
FanSpeedStatus_XX
SetRoomTemp_XX
RoomTemp_XX
Alarm_XX
MalfunctionCode_XX
UserModeCommand_XX
UserModeStatus_XX
Object Type
Indoor
Binary Output
Binary Input
Binary Value
Binary Input
Binary Input
Binary Value
Multistate Output
Multistate Input
Binary Output
Binary Input
Analog Value
Analog Input
Analog Value
Analog Input
Binary Input
Multistate Input
Multistate Output
Multistate Input
Vent
O
O
O
O
O
O
O
O
X
O
X
O
O
O
O
O
O
X
O
X
O
O
O
O
O
X
O
X
O
O
O
O
X
O
X
O

Hide quick links: