Environmental Requirements And Specifications; Temperature And Humidity; Altitude; Temperature And Humidity Requirements For Storage Expansion Enclosure When In Storage Or In Transit - IBM DS4000 EXP810 Installation, User's, And Maintenance Manual

Storage expansion enclosure
Table of Contents

Advertisement

Table 12. EXP810 shipping carton dimensions
Height
45.7 cm (18.0 in.)

Environmental requirements and specifications

This section describes the environmental requirements and specifications for the
storage expansion enclosure, including temperature and humidity, altitude, airflow
and heat dissipation, shock and vibration requirements, and acoustic noise levels.

Temperature and humidity

Table 13 lists the acceptable temperature and humidity ranges for the EXP810
storage expansion enclosure when in storage or in transit. Table 14 lists
temperature and humidity ranges for the storage expansion enclosure in typical
Information Technology (IT) or office environments. Table 21 on page 26 lists
temperature and humidity ranges for the storage expansion enclosure in a
Telco/NEBS-3 compliant environment.
Note: Substantial deviations from the suggested operating range, in either
Important: The recommended operating environment air temperature is 22° C (72°
Table 13. Temperature and humidity requirements for storage expansion enclosure when in
storage or in transit
Condition
Temperature
Relative humidity (no
condensation)
Table 14. Temperature and humidity requirements for storage expansion enclosure in a
typical Information Technology (IT) or office environment
Condition
Temperature
Relative humidity (no
condensation)

Altitude

Table 15 on page 21 lists the acceptable altitudes for operating, storing, and
shipping the EXP810.
20
IBM System Storage DS4000 EXP810 Storage Expansion Enclosure: Installation, User's and Maintenance Guide
Width
62.6 cm (24.5 in.)
direction, if sustained for extended periods of time, will expose the unit to
greater risk of failure from external causes.
F) or lower.
Parameter
Storage range
Maximum rate of change
Transit range
Maximum rate of change
Storage range
Transit range
Maximum dew point
Maximum gradient
Parameter
Operating range
Maximum rate of change
Operating range
Depth
80.7 cm (31.75 in.)
Requirement
-10° - 65° C (14° - 149° F)
15° C (27° F) per hour
-40° C to 65° C (-40° F to
149° F)
20° C (36° F) per hour
8% to 90%
5% to 95%
26° C (79° F)
10% per hour
Requirement
10° - 35° C (50° - 95° F)
10° C (18° F) per hour
8% to 80%

Advertisement

Table of Contents
loading