Liebert UPStation GXT 2U User Manual page 35

Hide thumbs Also See for UPStation GXT 2U:
Table of Contents

Advertisement

S
PECIFICATIONS
Model Number
Model Rating
DIMENSIONS: mm
Unit W x D x H: mm
Shipping W x D x H: mm
WEIGHT: kg
Unit: kg
Shipping: kg
INPUT AC PARAMETERS
Voltage Range
(typical)
100% - 90% loading
90% -70% loading
70% -30% loading
30% - 0% loading
Frequency
Input Connector
OUTPUT AC PARAMETERS
Output Sockets
Voltage
Frequency
Waveform
Main Mode
Overload
BATTERY PARAMETERS
Type
Qty x V x Rating
Battery Mfg/Part #
Back-up Time
Recharge Time
ENVIRONMENTAL
Operating Temp
Storage Temp
Relative Humidity
Operating Elevation
Storage Elevation
Audible Noise
AGENCY
Safety
RFI/EMI
Surge Immunity
Transportation
, C
ONTINUED
GXT2-2000RT230
2000VA / 1400W
87 x 547 x 430
268 x 692 x 585
24.7
28.7
176VAC / 280VAC
159VAC / 280VAC
139VAC / 280VAC
119VAC / 280VAC
IEC320-10A
(4) IEC320-10A
200/208/220/230/240 (user configurable) VAC; ±3%
130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, flame retardant, lead acid
4 x 12V x 9.0 AH
See 13.0 - Battery Run Times
5 Hours to 95% capacity after full discharge
into 100% load (Internal Batteries Only)
0°C to +40°C (+32°F to +104°F)
-15°C to +50°C (+5°F to +122°F)
Up to 3000 m (10,000 ft.) at 40°C (104°F) without derating
15,000 m (50,000 ft.) maximum
<55 dBA, at 1 metre from the rear
<50 dBA, at 1 metre from the front or sides
EN50091-1-1, CE compliance mark,
for both Low Voltage and EMC Directives
31
GXT2-3000RT230 / 3KRT230E
230 VAC nominal;
variable based on output load
176VAC / 280VAC
159VAC / 280VAC
139VAC / 280VAC
119VAC / 280VAC
40 - 70 Hz; Auto Sensing
50 Hz or 60 Hz
Sinewave
200% for 8 cycles;
Panasonic UP-VW1245P1
Yuasa / REW 45-12 FR
0% to 95%, non-condensing
EN 50091-2, Class B
EN 61000 4-2, 4-3, 4-4, 4-5
ISTA Procedure 1A
Specifications
3000VA / 2100W
87 x 618 x 430
268 x 692 x 585
31.9
35.9
IEC320-16A
(4) IEC320-10A,
(1) IEC320-16A
6 x 12V x 9.0 AH

Hide quick links:

Advertisement

Table of Contents
loading