7.3.3
You can set the frequency settings by inputting an analog voltage signal of -10 to +10Vdc between the VIB and
CC terminals.
The following shows examples when the run command is input from the terminal.
Title
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Power
Supply
7
* Connect a single-phase
input model to R/L1 and
S/L2/N.
Settings depending on voltage (-10 to +10 V) input
Function
Command mode selection
Frequency setting mode
selection
Analog input terminal
selection (VIB)
Analog/logic input selection
(VIA/VIB)
VIB input point 1 setting
VIB input point 1 frequency
VIB input point 2 setting
VIB input point 2 frequency
Analog input filter
MCCB
R/L1
VF-MB1
S/L2
T/L3
FLA
FLB
FLC
CC
VIB
PP
Adjustment range
0 – 4
0 – 11
0: 0-+10V
1: -10-+10V
0 – 4
0 - 100%
0.0 - 500.0Hz
0 - 100%
0.0 - 500.0Hz
2 - 1000 ms
Motor
U/T1
IM
V/T2
W/T3
Forward
run
F
Reverse
R
run
RES
S1
S2
S3
CC
Forward run
Reverse run
±
-10 to +10 Vdc
0
G-16
Default setting
Setting example
1
(panel keypad)
(terminal board)
0
(setting dial 1)
(terminal board VIB)
0
(-10 - +10V)
0
(Analog input)
0
0.0
100
*1
64
Run and stop settings
You can switch between forward run (F)
and reverser run (R), and run/stop with
external signals.
Setting characteristics for the
frequency setting signal and operation
frequency
Set characteristics at two points in the
diagram below.
Connecting and calibrating the
frequency meter
Select the type of meter connected at
and calibrate.
Refer to section 3.4 for details.
Operation frequency (Hz)
-100%
0%
100%
(-10V)
(0V)
(+10V)
Frequency setting signal
E6581697
0
2
1
0
0
0.0
100
50.0/60.0
64
Point 2
%
Point 1