Toshiba TOSVERT VF-MB1 Instruction Manual page 23

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

1.3.3
1) Power circuit terminal
1
Models
Terminal
Input
Output
Earth
(For input)
Earth
(For output)
M3 screw
Earth terminal
(M4 screw)
M3 screw
EMC plate
Power circuit and control circuit terminal boards
In case of the lug connector, cover the lug connector with insulated tube, or use the insulated lug
connector.
Use a plus or minus screwdriver to loose or tighten screws.
VFMB1S-2002 to 2022PL
VFMB1-4004 to 4037PL
Screw size
Torque
M3
0.6Nm
5.3lb  in
M3
0.8Nm
7.1lb  in
M5
3.0Nm
26.6lb  in
M4
1.4Nm
12.4lb  in
Refer to section 2.3.1 for details about terminal functions.
VFMB1S-2002 to 2007PL
R/L1
S/L2/N
PBe PB U/T1 V/T2 W/T3
VFMB1-4055 to 4150PL
Strip length
Screw size
7-8mm
M4
9-10mm
-
M5
-
VFMB1S-2015, 2022PL
R/L1
PBe PB U/T1 V/T2 W/T3
A-10
E6581697
Torque
Strip length
1.4Nm
12.4lb  in
9-10mm
3.0Nm
26.6lb  in
-
M3 screw
S/L2/N
Earth terminal
(M4 screw)
M3 screw
EMC plate

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents