Toshiba TOSVERT VF-MB1 Instruction Manual page 126

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-MB1:
Table of Contents

Advertisement

6.2.2
f107 : Analog input terminal selection (VIB)
 Function
[Parameter setting]
f107
f107 = 0 : Input 0 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between 0 to +10Vdc.
f107 = 1 : Input -10 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between -10 to +10Vdc.
6.2.3
6
f109 : Analog/logic input selection (VIA/VIB)
 Function
[Parameter setting]
f109
Note) When using VIA and VIB terminals as contact input terminals, be sure to insert a resistor between P24
Changing the voltage range of VIB terminal
This parameter allows you to choose the voltage signal input for the VIB terminal.
Title
Function
Analog input terminal
selection (VIB)
Changing the functions of VIA and VIB terminals
This parameter allows you to choose between analog signal input and contact signal input for the VIA
and VIB terminals.
Title
Function
Analog/logic input
selection
(VIA/VIB)
terminal and VIA/VIB terminals in sink logic connection, and insert a resistor between VIA/VIB terminals
and CC terminal in source logic connection. (Recommended resistance: 4.7k  -1/2W)
Adjustment range
0: 0-+10V
1: -10-+10V
Adjustment range
0: Analog input for communications
VIB - analog input
1: VIA - analog input
VIB - contact input (Sink)
2: VIA - analog input
VIB - contact input (Source)
3: VIA - contact input (Sink)
VIB - contact input (Sink)
4: VIA - contact input (Source)
VIB - contact input (Source)
F-6
E6581697
Default setting
0
Default setting
0