Built-in EtherNet/IP Port (Port 1) Indicators

Indicator
NET RUN
Green
NET ERR
Red
LINK/ACT
Yellow
3-6
Color
Status
Lit
Normal startup status.
Flashing
Ethernet communications are in progress.
• Tag data link connection establishment in progress.
• IP address acquisition with BOOTP in progress.
Not lit
You cannot perform Ethernet communications.
• The power supply is OFF or the CPU Unit was reset.
• A MAC address error or communications Controller error
Lit
An error for which the user cannot recover operation occurred.
• A MAC address error or communications Controller error
Flashing
An error for which the user can recover operation occurred.
• An error occurred in TCP/IP communications or CIP communi-
• FTP server setting error, NTP server setting error, etc.
• Tag data link setting error, tag data link verification error, etc.
Not lit
There are no Ethernet communications errors.
• The power supply is OFF or the CPU Unit was reset.
Lit
The link was established.
Flashing
The link is established, and data communications are in progress.
Not lit
A link was not established.
• The cable is not connected.
• The power supply is OFF or the CPU Unit was reset.