Event name
Illegal User Program Execution ID
Meaning
The user program execution IDs set in the user program and in the CPU Unit do not match.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The user program execution IDs set in
the user program and in the CPU Unit
do not match.
A user program execution ID is set in
the CPU Unit but not in the user pro-
gram.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
Event name
Illegal User Program
Meaning
The user program is not correct.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
The limit to the number of nesting lev-
els for functions or function blocks
was exceeded.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-6.
NJ-series CPU Unit Hardware User's Manual (W500)
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Set the same user program execution
ID in the user program and CPU Unit.
If user program execution ID is not set
in the user program, clear the user
program execution ID set in the CPU
Unit by clearing all memory in the
CPU Unit.
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Find the location in the user program
that exceeds the limit to the number of
nesting levels for functions or function
blocks and reduce the number of
nesting levels to within the limit. Then,
download the user program again.
5 Troubleshooting
Event code
10210000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Stops.*
Name
---
Prevention
Set the same user program execution
ID in the user program and CPU Unit.
Keep a record of the user program
execution IDs set in the user program
and in the CPU Unit. They are not dis-
played.
Event code
10240000 hex
None
Detection
timing
Cycle the power
Log category
supply or reset
the Controller.
Stops.*
Name
---
Prevention
Write the user program so that the
limit to the number of nesting levels
for functions or function blocks is not
exceeded. Use the program check on
the Sysmac Studio to confirm that the
limit to the number of nesting levels is
not exceeded.
At user program
download, power
ON, or Controller
reset
System
5
At download,
power ON, or
Controller reset
System
5-45