Troubleshooting Chart - Amana AMV9 Installation Instructions Manual

Two-stage variable speed gas-fired warm air furnace
Hide thumbs Also See for AMV9:
Table of Contents

Advertisement

Symptoms of Abnormal
Operation
• Furnace fails to operate.
• Integrated control module
diagnostic LED provides
no signal.
• Furnace fails to operate.
• Integrated control module
diagnostic LED is lit
continuously.
• Furnace fails to operate.
• Integrated control module
diagnostic LED is
flashing ONE (1) flash.
• Furnace fails to operate.
• Integrated control module
diagnostic LED is
flashing TWO (2) flashes.
• Induced draft blower runs
continuously with no
further furnace operation.
• Integrated control module
diagnostic LED is
flashing THREE (3)
flashes.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
TR
TR
TROUBLESH
OUBLESH
OUBLESH
OUBLESHOO
TR
TR
OUBLESH
Associated
Fault Description(s)
LED Code
2
NONE
• No 115 volt power to
furnace, or no 24 volt
power to integrated
control module.
• Blown fuse or circuit
breaker.
• Integrated control
module has an
internal fault.
• No signal from
ON
thermostat.
CONTINUOUS
ON
• Furnace lockout due
1
to an excessive
number of ignition
1
"retries" (3 total)
1 FLASH
• Pressure switch
2
circuit is closed.
• Induced draft
blower is not
2 FLASHES
operating.
• Pressure switch
circuit not closed.
3
• Induced draft blower
is operating.
3 FLASHES
OO
OO
OOTIN
TIN
TIN
TING CHAR
G CHAR
G CHART T T T T
G CHAR
OO
TIN
G CHAR
Possible Causes
• Manual disconnect switch
OFF, door switch open, or
24 volt wires improperly
connected or loose.
• Blown fuse or circuit
breaker.
• Integrated control module
has an internal fault.
• Improper thermostat
connection or setting.
• Failure to establish flame.
Cause may be no gas to
burners, front cover
.
pressure switch stuck
open, bad igniter or igniter
alignment, improper
orifices, or coated/oxidized
or improperly connected
flame sensor.
• Loss of flame after
establishment. Cause may
be interrupted gas supply,
lazy burner flames
(improper gas pressure or
restriction in flue and/or
combustion air piping),
front cover pressure switch
opening, or improper
induced draft blower
performance.
• Induced draft blower
pressure switch contacts
sticking.
• Shorts in pressure switch
circuit.
• Pressure switch hose
blocked, pinched or
connected improperly.
• Blocked flue and/or inlet air
pipe, blocked drain system,
or weak induced draft
blower.
• Incorrect pressure switch
setpoint or malfunctioning
switch contacts.
• Loose or improperly
connected wiring.
37
Corrective Action
Cautions and Notes
• Assure 115 and 24 volt
• Turn power OFF
power to furnace
prior to repair.
integrated control module.
• Replace integrated
• Check integrated control
control module
module fuse (3A).
fuse with 3A
Replace if necessary.
automotive fuse.
• Check for possible shorts
• Read precautions
in 115 and 24 volt circuits.
in "Electrostatic
Repair as necessary.
Discharge" section
of manual.
• Replace bad integrated
control module.
• Check thermostat
• Turn power OFF
connections and settings.
prior to repair.
• Improper thermo-
stat connection or
setting.
• Turn power
• Locate and correct gas
OFF prior to
interruption.
repair.
• Check front cover
pressure switch
operation (hose, wiring,
contact operation).
Correct if necessary.
• Replace or realign
• Igniter is
igniter.
fragile, handle
• Check flame sense
with care.
signal. Sand sensor if
• Sand flame
coated and/or oxidized.
sensor with
• Check flue piping for
emery cloth.
blockage, proper
• See "Vent/Flue
length, elbows, and
Pipe" section
termination.
for piping
• Verify proper induced
details.
draft blower perfor-
mance.
• Replace induced draft
• Turn power OFF
blower pressure switch.
prior to repair.
• Replace pressure
switch with proper
• Repair short.
replacement part.
• Inspect pressure
• Turn power
switch hose. Repair, if
OFF prior to
necessary,
repair.
• Inspect flue and/or inlet
• Replace
air piping for blockage,
pressure
proper length, elbows,
switch with
and termination. Check
proper
drain system. Correct
replacement
as necessary.
part.
• Correct pressure switch
setpoint or contact
motion.
• Tighten or correct
wiring connection.