Ropane As Anks And Iping - Amana AMV9 Installation Instructions Manual

Two-stage variable speed gas-fired warm air furnace
Hide thumbs Also See for AMV9:
Table of Contents

Advertisement

Connect the furnace to the building piping by one of the
following methods:
Rigid metallic pipe and fittings.
Semi-rigid metallic tubing and metallic fittings.
Aluminum alloy tubing must not be used in exterior
locations. In order to seal the grommet cabinet
penetration, rigid pipe must be used to reach the outside
of the cabinet. A semi-rigid connector to the gas piping
may be used from there.
Use listed gas appliance connectors in accordance with their
instructions. Connectors must be fully in the same room as
the furnace.
Protect connectors and semirigid tubing against physical and
thermal damage when installed. Ensure aluminum-alloy tubing
and connectors are coated to protect against external
corrosion when in contact with masonry, plaster, or insulation,
or subjected to repeated wetting by liquids such as water
(except rain water), detergents, or sewage.
GAS VALVE
MANIFOLD
BURNERS
ALTERNATE
GAS LINE
LOCATION
PLUG IN
ALTERNATE
GAS L INE
HEIGHT REQUIRED
HOLE
BY LOCAL CODE
GROUND JOINT
PIPE UNION
DRIP LEG
UPFLOW
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION)
GROUND JOINT
PIPE UNION
DRIP LEG
GROMMET IN STANDARD
GAS VALVE
GAS LINE HOLE
BURNERS
DRAIN TRAP
PLUG IN ALTERNATE
MANIFOLD
GAS LINE HOLE
ALTERNATE GAS
LINE LOCATION
HORIZONTAL [UPFLOW MODEL]
NOTES
1. WHEN GAS LINE IS IN THE ALTERNATE
:
LOCATION
SWAP THE POSITION OF
,
THE PLUG AND GROMMET
.
Gas Piping Connections
E
DGES OF SHEET METAL HOLES MAY BE SHARP.
WHEN REMOVING HOLE PLUGS.
D
/S
I
P
IRECT
TANDARD
NLET
IPING
When gas piping enters directly to the gas valve through the stan-
dard inlet hole, the installer must supply straight pipe with a ground
joint union to reach the exterior of the furnace. The rigid pipe must
be long enough to reach the outside of the cabinet to seal the grom-
met cabinet penetration. A semi-rigid connector to the gas piping
can be used outside the cabinet per local codes.
MANUA L
SHUT OFF V ALVE
(UPSTREAM FROM
ALTERNATE
MANUAL
GROUND JOINT
GAS LINE
SHUT OFF VALVE
PIPE UNION)
LOCATION
(UPSTREAM FROM
GROUND JOINT
PIPE UNION)
HEIGHT REQUIRED
BY LOCAL CODE
GROMMET
IN STANDARD
GAS LINE HOLE
GROMMET
IN STANDARD
GAS LINE HOLE
DRIP LEG
GROUND JOINT
P IPE UNION
COUNTERFLOW
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION)
GROUND JOINT
PIPE UNION
DRIP LEG
GROMMET IN STANDARD
GAS VALVE
GAS LINE HOLE
BURNERS
DRAIN TRAP
MANIFOLD
PLUG IN ALTERNATE
ALTERNATE
GAS LINE HOLE
GAS LINE LOCATION
HORIZONTAL[COUNTERFLOW]
2. DRIP LEG MAY TERMINATE WITH
A 1/2" X 1/8" PIPE PLUG TO
ACCOMMODATE LINE GAS
PRESSURE MEASUREMENT.
CAUTION
U
SE GLOVES A PRECAUTION
I
/A
NDIRECT
LTERNATE
When gas piping enters indirectly to the gas valve through the alter-
nate gas inlet hole the following fittings (starting from the gas valve)
to reach the outside of the cabinet must be supplied:
Coupling.
90 degree elbow.
2 inch close nipple.
90 degree elbow.
Straight pipe, with a ground joint union, to reach the exterior
of the furnace. The rigid pipe must be long enough to reach
the outside of the cabinet so as to seal the grommet cabinet
penetration. A semi-rigid connector to the gas piping can be
used outside the cabinet per local codes.
G
P
C
AS
IPING
HECKS
Before placing unit in operation, leak test the unit and gas connec-
tions.
T
O AVOID THE POSSIBILITY OF EXPLOSION OR FIRE, NEVER USE A MATCH OR
OPEN FLAME TO TEST FOR LEAKS.
PLUG IN
ALTERNATE
Check for leaks using an approved chloride-free soap and water
GAS LINE
HOLE
solution, an electronic combustible gas detector, or other approved
testing methods.
GAS VALVE
MA NIFOLD
NOTE: Never exceed specified pressures for testing. Higher
BURNERS
pressure may damage the gas valve and cause subsequent
overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping
system before pressure testing the supply piping system with pres-
sures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by closing its
external manual gas shutoff valve before pressure testing supply
piping system with test pressures equal to or less than 1/2 psig (3.48
kPa).
P
G
T
ROPANE
AS
ANKS AND
P
ROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN SETTLE IN
ANY LOW AREAS OR CONFINED SPACES.
PERSONAL INJURY, OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A
PROPANE GAS LEAK, INSTALL A GAS DETECTION WARNING DEVICE.
A gas detecting warning system is the only reliable way to detect a
propane gas leak. Rust can reduce the level of odorant in propane
gas. Do not rely on your sense of smell. Contact a local propane
gas supplier about installing a gas detecting warning system. If the
presence of gas is suspected, follow the instructions on Page 4 of
this manual.
All propane gas equipment must conform to the safety standards of
the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 11 inch
w.c. at the furnace manifold with all gas appliances in operation.
Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid,
and "wetted surface" area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
25
I
P
NLET
IPING
WARNING
P
IPING
WARNING
T
O PREVENT PROPERTY DAMAGE,