Table 2 Inverter Mode Specifications - MPP Solar PIP-MS 1-5KVA User Manual

Inverter / charger (800w-4kw)
Table of Contents

Advertisement

Table 2 Inverter Mode Specifications

INVERTER MODEL
Rated Output Power
Output Voltage Waveform
Output Voltage Regulation
Output Frequency
Peak Efficiency
Overload Protection
Surge Capacity
Nominal DC Input Voltage
Cold Start Voltage
Low DC Warning Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Warning Return Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
Low DC Cut-off Voltage
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
High DC Recovery Voltage
High DC Cut-off Voltage
No Load Power Consumption
Saving Mode Power Consumption
*4KVA/5KVA only supports 230VAC system.
1KVA 24V
2KVA 24V
3KVA 24V
2KVA 24V Plus
3KVA 24V Plus
1KVA/0.8KW
2KVA/1.6KW
3KVA/2.4KW
110/120VAC
5s@≥150% load; 10s@110%~150% load
2* rated power for 5 seconds
24Vdc
23.0Vdc
22.0Vdc
21.4Vdc
20.2Vdc
23.0Vdc
22.4Vdc
21.2Vdc
21.0Vdc
20.4Vdc
19.2Vdc
29Vdc
31Vdc
<25W
<10W
28
1KVA 48V
3KVA 48V
2KVA 48V Plus
3KVA 48V Plus
1KVA/1KW
2KVA/1.6KW
3KVA/2.4KW
Pure Sine Wave
±5%*
230Vac±5%
or
60Hz or 50Hz
90%
48Vdc
46.0Vdc
44.0Vdc
42.8Vdc
40.4Vdc
46.0Vdc
44.8Vdc
42.4Vdc
42.0Vdc
40.8Vdc
38.4Vdc
58Vdc
62Vdc
4KVA
5KVA
4KVA/3.2KW
5KVA/4KW
60Vdc
<50W
<15W