PV Module Selection:
When selecting proper PV modules, please be sure to consider below parameters:
1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter.
2. Open circuit Voltage (Voc) of PV modules should be higher than min. battery voltage.
Solar Charging Mode
INVERTER MODEL
Max. PV Array Open Circuit Voltage
PV Array MPPT Voltage Range
Min. battery voltage for PV charge
Please follow below steps to implement PV module connection:
1. Remove insulation sleeve 10 mm for positive and negative conductors.
2. Check correct polarity of connection cable from PV modules and PV input
connectors. Then, connect positive pole (+) of connection cable to positive
pole (+) of PV input connector. Connect negative pole (-) of connection
cable to negative pole (-) of PV input connector.
3. Make sure the wires are securely connected.

Final Assembly

After connecting all wirings, please put bottom cover back by screwing two screws as shown below.
1KVA 24V
2KVA 24V
3KVA 24V
75Vdc max
30~66Vdc
17Vdc
1KVA/2KVA/3KVA
2KVA 24V
1KVA 48V
Plus/ 3KVA
3KVA 48V
24V Plus
102Vdc max
60~88Vdc
34Vdc
2KVA Plus/3KVA Plus/4KVA/5KVA
9
2KVA 48V
Plus/3KVA 48V
Plus/ 4KVA/5KVA
145Vdc
30~115Vdc
60~115Vdc
17Vdc
34Vdc