Water Connections - Bosch C 950 ES Installation Manual

Temperature modulated with electronic ignition suitable for heating potable water and space heating
Hide thumbs Also See for C 950 ES:
Table of Contents

Advertisement

3.9

Water connections

Warning: This heater is not approved
for
preheated
exceeding 140°F (60°C).
Warning:
In
applications
temperature can exceed 140°F (60ºC), a
3-way valve or mixing valve must be
installed before the appliance to prevent
water exceeding 140°F (60°C) from
entering the appliance.
B When facing the heater, the ¾" cold connection is on
the bottom right and the hot connection is on the bot-
tom left. Centrally locating the water heater is recom-
mended to keep hot water distribution times even
throughout the structure.
HOT
Fig. 32
Fig. 33 Water filter
1
Water valve with engine
2
Water filter
B The use of unions when connecting both water
pipes to the inlet and outlet connections is
required. This will facilitate any necessary
servicing.
6 720 646 812
water
applications
where
inlet
water
COLD
B Plastic or PEX type plumbing line materials are not
suitable for connecting directly to the water heater.
B Although water piping throughout the building may
be other than copper, we recommend that copper or
suitably rated stainless steel flex line piping be used
for the water connections for 1.5' on either side of
the water heater (follow local codes if more
stringent).
B Never sweat any piping directly to or beneath
the water connections, as damage will occur to
the internal water valve from heating of the
pipe.
B Keep water inlet and outlet pipes to no less
than ¾" (19.05mm) diameter to allow the full
flow capacity.
B If the cold and hot connections to the heater are
reversed, the heater will not function. Be certain there
are no loose particles or dirt in the piping. Blow out
or flush the lines before connecting to the water
heater.
B Full port shutoff valves should be installed on
both the cold water supply and hot water outlet
lines to facilitate servicing the heater (see Fig.
34).
B For installation on a private well system with the use
of a pressure tank, the lowest pressure range setting
recommended is 40-60 psi (2.75 - 4.15bar).
3.10 Water quality
Water quality can have an impact on appliance
longevity and may void the manufacturer's warranty.
For water analysis data call your local water department,
or if on a well, have well water analyzed periodically. If
water quality exceeds one or more of the values
specified below, Bosch recommends consulting a local
water treatment professional for water softening/
conditioning options.
Description
pH
TDS (total Dissolved Solids) mg/l or ppm
Total hardness
Aluminum
Chlorides
Copper
Iron
Manganese
Zinc
Table 20
Installation instructions
Max. Levels
pH
6.5 - 8.5
500
100 (6
mg/l or ppm
grains)
mg/l or ppm
2.0
mg/l or ppm
250
mg/l or ppm
1.0
mg/l or ppm
0.3
mg/l or ppm
0.05
mg/l or ppm
5.0
29