Low Pressure Protection Control - Daikin VRV II-Q RQYQ8-48PY1B Service Manual

R-410a 50hz heat pump
Table of Contents

Advertisement

Detailed Control Functions

2.5.2 Low Pressure Protection Control

This low pressure protection control is used to protect compressors against the transient decrease of low
pressure.
[In cooling]
In case of multi-outdoor-unit system, the following control is performed in the entire system.
(3 times per 60 minutes at max.)
52
Normal operation
Pe < 0.34 MPa
*1
(
0.20 MPa)
All STD compressors stop
Pe < 0.25 MPa
*1
(
0.15 MPa)
Master unit: 52 Hz + OFF + OFF
Slave unit: ALL unit stop
Pe < 0.15 MPa
*1
(
0.10 MPa)
Solenoid valve (hot gas) (Y1S): ON
Pe < 0.07 MPa
Restart standby
Pe > 0.39 MPa
Pe: Low pressure sensor detection value
for master unit
*1
Value in the thermal storage operation
Pe > 0.29 MPa
Low pressure standby
4 times within 60 minutes
Stop due to error
E4
("
" displayed)