System set up

Hardware link

Electronic module
P1
1
P19
2
3
To allow data to
be saved to EEPROM
To write protect
the EEPROM
When making changes to the panel set up
the modified data must be saved to the
EEPROM. To save the data to the
EEPROM a hardware link located on the
electronic module inside the panel must be
configured.
With the front door open the hardware link is
C128
visible mid-way on the bottom face of the
electronic module.
To allow the changed data to be saved to
the EEPROM, a hardware link must be
configured first.
P1
1
2
Configure the link P1 to position 1-2.
3
It is advisable to always leave the panel with
the link P1 in the protected position.
P1
1
2
3
Configure the link P1 to position 2-3.
Only a trained person must
attempt any changes to the
hardware link.
796689 (4188-658) i2__04/07
23