To exit Fire test
mode
After the fire test on manual call point is
complete the panel must be taken out of the
test mode and returned to normal operating
condition.
A2
Enter access level 2.
Press Enter to display the top level menu
From the System menu select Fire Test
option and press Enter to accept the
selection.
Press Enter to exit fire test.
The fire test mode has been exited and the
Test light switches Off.
In Test State all normal fire
detection functions are disabled.