Service Inspection Guide - IBM T00 Service Manual

7014 series system rack
Table of Contents

Advertisement

Service Inspection Guide

Perform a service inspection on the rack when any of the following conditions occur:
The rack is inspected under a maintenance agreement.
v
v Service is requested and service has not recently been performed.
v An alterations-and-attachments review is performed.
v Changes have been made to the equipment that might affect the safe operation of the equipment.
v External devices with an attached power cord are connected to the rack.
If the inspection indicates an unacceptable safety condition, the condition must be corrected before
representatives service the machine.
Note: The correction of any unsafe condition is the responsibility of the owner of the system.
Do the following checks:
1. If the rack is bolted down, do the following:
a. Ensure that the rack is firmly secured to the floor.
b. Ensure that the four plastic isolator bushings are under the four leveling feet (dc only).
1 Rack-Mounting Bolt
2 Thin Washer
3 Top Plastic Isolator Bushing
4 Thick Washer
5 Spacer
6 Jam Nut
14
7014 Model T00, and Model T42 Service Guide
1
2
3
4
5
6
7
8
9
10
11
12
9
7 Leveling Foot
8 Lower Plastic Isolator Bushing (Used
only on dc powered systems)
9 Mounting Plate
10 Threaded Hole (Used to secure the
rack to mounting plate.)
11 Anchor Bolt Hole
12 Traced Pattern (Pattern to be traced
onto the floor using the mounting
plate as a template)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T427014 t007014 t42

Table of Contents