Trouble Shooting
Display
Title
code
D-pipe (Inverter)
temp. high
32
(105˚C )
D-pipe (Constant)
33
temp. high
(105˚C )
Check Flow Chart
Check Over load condition
- Refrigerant leakage
- Condenser is blocked
- Outdoor fan is locked
Yes
Unplug the sensor
on Outdoor unit PCB
Check the
Connector connection
Is it normal ?
Yes
Estimate the resistance
of each sensor.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Discharge sensor
(Inverter) temp. high
• Discharge sensor
(Cons.) temp. high
No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Correct connection
- 76 -
Check point & Normal condition
• Check the discharge pipe sensor for INV.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.
• Refer to sensor resistance table.
• Check the discharge pipe sensor for Cons.
• Check the install condition for over load.
• Check the leakage of refrigerant.
• Check the SVC V/V open.
• Refer to sensor resistance table.
Is the resistance of the
sensor is 200kΩ
at 25˚C?
Yes
Plug the sensor
on Indoor unit PCB
Estimate the Voltage
of each sensor.
Yes
Is the voltage of the
sensor is
4.5Vdc at 25˚C
Yes
Repair or Change the PCB.
No
Change the sensor
No
Change the sensor
LGE Internal Use Only