LG AH-W096A0 Service Manual page 69

Lg thermav system ah series air conditioners
Table of Contents

Advertisement

Display
Title
code
22
Max. C/T
Check Flow Chart
Check the wire
connection.(U,V,W)
Is it normal ?
Yes
Check the resistance of
comp. (No difference at
each terminal)
Is it normal ?
Yes
Check the electricity
leakageof the compressor.
(Refer to comp check table)
Is it normal ?
Yes
Check the input power
(Outdoor, Indoor unit)
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Cause of error
• Over current
No
Correct
connection
No
Change
Compressor
❊ Dc link voltage table
No
Change
Model
Compressor
1 Phase
3 Phase
- 69 -
Check point & Normal condition
• Malfunction of compressor
• Blocking of pipe
• Low voltage input
• Refrigerant, pipe length, blocked, ...
Is it normal ?
(1 Ph : 230V ±10%
3 Ph : 400V ±10% )
Yes
Check DC link
capacitor Is it normal?
(Refer to belows)
Yes
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked
No
Change Main PCB
Type
Non operating
AUUW126C
PSC
DC300V ¡¾ 10%
AUUW186C
PSC
DC300V ¡¾ 10%
AUUW246D
PFC
DC300V ¡¾ 10%
AUUW306D
PFC
DC300V ¡¾ 10%
AUUW366D
PFC
DC300V ¡¾ 10%
AUUW426D
PFC
DC300V ¡¾ 10%
AUUW486D
PFC
DC300V ¡¾ 10%
AUUW606D
PFC
DC300V ¡¾ 10%
AUUW368D
PSC
DC540V ¡¾ 10%
AUUW428D
PFC
DC540V ¡¾ 10%
AUUW488D
PFC
DC540V ¡¾ 10%
AUUW608D
PFC
DC540V ¡¾ 10%
Trouble Shooting
No
Needs electric work
No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
DC Link Voltage
Operating
DC280V ¡¾ 10%
DC280V ¡¾ 10%
DC380V ¡¾ 10%
DC380V ¡¾ 10%
DC380V ¡¾ 10%
DC380V ¡¾ 10%
DC380V ¡¾ 10%
DC380V ¡¾ 10%
DC500V ¡¾ 10%
DC680V ¡¾ 10%
DC680V ¡¾ 10%
DC680V ¡¾ 10%
LGE Internal Use Only