Electronic Expansion Valve - LG AH-W096A0 Service Manual

Lg thermav system ah series air conditioners
Table of Contents

Advertisement

Checking Key Components of Outdoor Unit

2.3 Electronic Expansion Valve

EEV
M
1
• Pulse signal output value and valve operation
Output(ø) No.
ø1
ø2
ø3
ø4
• Output pulse sequence
- In valve close state: 1
- In valve open state: 8 ¡ 7 ¡ 6 ¡ 5 ¡ 4 ¡ 3 ¡ 2 ¡ 1 ¡ 8
1. If EEV open angle does not change, all of output phase will be OFF
2. If output phase is different or continuously in the ON state, motor will not operate smoothly and start vibrat-
ing.
• EEV valve operation
Valve
close
open
Angle
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
ø5
4
ø4
6
ø3
2
3
Orange
ø2
ø1
1
2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
OFF
¡ 2 ¡ 3 ¡ 4 ¡ 5 ¡ 6 ¡ 7 ¡ 8 ¡ 1
Full open
open
1350 pulses
pulse
Red
5
White
4
Yellow
3
2
Blue
1
Output state
3
4
5
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
- At power ON, open angle signal of 1400 pulses out-
put and valve position is set to
If valve operates smoothly, no noise and vibration
occurs and if valve is closed. noise occurs.
- Noise from EEV can be confirmed by touching the
EEV surface with a screw driver and listening the
EEV noise.
- If liquid refrigerant is in EEV, the noise is lower.
- 56 -
DC 12V
Driving
circuit
ø4
ø3
ø2
ø1
6
7
8
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents